The XHJB666 Microcomputer Relay Protection Calibrator is a state-of-the-art 6-phase voltage and 6-phase current test instrument built on a high-performance embedded industrial control computer with an 8.4-inch TFT color LCD display. Unlike conventional 3-phase calibrators limited to basic overcurrent and distance relay testing, the 6-phase architecture supports all standard configurations—including 4-voltage 3-current, 6-voltage, 6-current, and 12-phase output modes—enabling comprehensive testing of the most complex modern protection schemes: transformer differential protection (multi-winding), busbar differential protection (multi-feeder), generator protection (stator earth fault, loss of excitation), and line differential protection with communication-assisted schemes.
At the heart of the instrument is a DSP-controlled output stage driving high-fidelity modular linear power amplifiers rather than switching-type amplifiers. This fundamental design decision eliminates the high-frequency switching noise inherent in Class-D amplifiers, delivering clean sinusoidal waveforms with harmonic distortion suitable for testing the most sensitive digital relays. The DSP processor provides real-time digital signal processing with high-resolution D/A conversion and controlled transmission bandwidth, enabling precise waveform synthesis including harmonics up to the 20th order, DC offset components, and user-defined transient waveforms for fault playback simulation. A 10-channel digital input and 8-channel digital output interface connects directly to relay trip and close contacts with intelligent auto-recognition of dry contacts (1–20mA, 24V) and potential contacts (0–250V). Independent 110V and 220V adjustable DC auxiliary outputs power relay coils and trip circuits during field testing.
![]()
| Parameter | Specification |
|---|---|
| 6-Phase Output (per phase) | 0 – 30A (RMS) |
| 3-Phase Output (per phase) | 0 – 60A (RMS) |
| 6-Phase Parallel Output | 0 – 180A (10s maximum) |
| Long-Term Phase Current | 10A (RMS) |
| Maximum Output Power (per phase) | 400VA |
| Output Accuracy | ≤0.5A: ±2mA; >0.5A: 0.2% |
| Frequency Range (Fundamental) | 0 – 1000Hz |
| Harmonic Capability | 1st – 20th order |
| Parameter | Specification |
|---|---|
| Output Range | 0 – ±10A per phase / 0 – 20A two-phase superimposed |
| Output Accuracy | 0.5% |
| Maximum Load Voltage | 20V |
| Parameter | Specification |
|---|---|
| Phase Voltage Output (RMS) | 0 – 120V |
| Line Voltage Output (RMS) | 0 – 240V |
| Output Accuracy | 0.2% |
| Phase/Line Output Power | 80VA / 100VA |
| Frequency Range (Fundamental) | 0 – 1000Hz |
| Harmonic Capability | 1st – 20th order |
| Parameter | Specification |
|---|---|
| Phase Voltage Output | 0 – ±160V |
| Line Voltage Output | 0 – 320V |
| Output Accuracy | 0.5% |
| Phase/Line Output Power | 70VA / 140VA |
| Parameter | Specification |
|---|---|
| Digital Inputs | 10 channels (auto-detection: dry contact 1–20mA/24V or potential contact 0–250V) |
| Digital Outputs | 8 pairs (DC: 220V/0.2A; AC: 220V/0.5A) |
| Time Measurement Range | 0.1ms – 9999s |
| Time Measurement Accuracy | <0.1ms |
| Auxiliary DC Output | Independent adjustable 110V and 220V DC |
| Parameter | Specification |
|---|---|
| Dimensions | 480 × 360 × 200 mm |
| Weight | 19 kg |
| Display | 8.4-inch TFT color LCD |
| Amplifier Type | DSP-controlled high-fidelity modular linear amplifier |
| Optional | GPS synchronous trigger for end-to-end testing |
Unlike basic 3-phase relay test sets that suffice for simple overcurrent relay verification, the XHJB666 is purpose-built for organizations where comprehensive multi-phase protection scheme testing—not just individual relay calibration—determines commissioning quality and operational safety:
◆ Power Utility Protection & Control Departments — Grid operators responsible for commissioning and periodic testing of transmission and distribution protection systems. The 6-phase architecture tests transformer differential protection (Restricted Earth Fault, biased differential), busbar differential schemes, and distance protection with power swing blocking in a single instrument session. The GPS sync option enables end-to-end testing of line current differential and phase comparison protection schemes across substations separated by tens of kilometers—a capability that 3-phase test sets cannot provide.
◆ Electrical Commissioning & Relay Testing Service Providers — Independent testing companies providing protection system commissioning for new substation construction, upgrade projects, and periodic maintenance contracts. The XHJB666’s combination of 6-phase capability, 0.2% accuracy, and automated test software reduces per-relay testing time by 40–60% compared with manual methods, while the 180A parallel current output tests instantaneous trip elements that lower-current testers cannot exercise. The real-time data storage, vector graphics display, and report printing deliver the documentation quality required for contractual commissioning sign-off.
◆ Generator & Large Motor Protection Testing — Power plants and industrial facilities testing generator protection schemes including stator earth fault (100%), loss of excitation (40#), reverse power, negative sequence overcurrent, and out-of-step protection. Generator protection requires simultaneous multi-phase voltage and current injection with precise phase angle control—the 6-phase architecture provides sufficient channels to simulate the full generator terminal conditions for comprehensive protection verification.
◆ Railway Traction Power & Industrial Substation Maintenance — Railway electrification systems, mining substations, and heavy industrial plants operating special protection schemes (frame leakage, pilot wire differential, arc flash detection). The instrument’s independent 110V/220V DC auxiliary supply powers protection relays and trip circuits during testing when the station battery is unavailable or isolated for safety, while the 10-channel DI intelligently handles the diverse contact types found across mixed-vintage protection installations.
Q1: Why is a 6-phase calibrator necessary when most protection testing only requires 3-phase output?
While simple overcurrent and earth fault relays can be tested with 3-phase output, modern numerical protection schemes demand significantly more channels: Transformer differential protection requires 4–6 current channels (HV side 3-phase + LV side 3-phase) to simulate through-fault and internal fault conditions correctly. Busbar differential schemes may require 4 phase voltage + 3 phase current channels for directional comparison. Generator protection testing needs 3-phase voltage + 3-phase current for stator fault and loss-of-field testing. Distance protection with power swing blocking and communication-aided schemes requires voltage and current vectors that a 3-channel unit cannot produce simultaneously without repeated reconnection. The XHJB666’s 6V+6I channels test these schemes in a single setup: a transformer differential test that requires 4–5 hours of sequential testing with a 3-phase set can be completed in 1–1.5 hours with the 6-phase architecture.
Q2: What is the advantage of the linear power amplifier over a switching (Class-D) amplifier in a relay test set?
Linear amplifiers reproduce the input waveform through continuously variable transistor conduction without the high-frequency switching (typically 100–500 kHz) used in Class-D designs. For relay testing, this matters in three critical ways: (1) Waveform fidelity—linear amplifiers produce inherently broadband, low-distortion outputs without the switching residual and output filtering artifacts that can confuse digital relays sampling at high rates. (2) Transient response—when simulating fault conditions with DC offset, the linear amplifier responds instantly without the output filter ringing that occurs when a Class-D amplifier encounters a sudden load change. (3) Electro-magnetic compatibility—no high-frequency switching means no radiated EMI that could affect nearby unshielded protection relays or communications equipment in the test bay. The trade-off is higher weight and power consumption—acceptable in a professional instrument where measurement integrity cannot be compromised.
Q3: When is the 180A 6-phase parallel current output needed?
The 180A parallel mode serves several essential testing scenarios not possible with lower-current test sets: (1) Circuit breaker trip coil and mechanism verification—injecting high current through the CT secondary circuit to test the complete protection chain from relay output through trip coil to breaker mechanism operation. (2) Instantaneous overcurrent element testing on relays with high pickup settings—parallel output into a single phase achieves the high current needed to verify I>> settings that single-phase 30A cannot reach. (3) Primary injection simulation—testing the relay CT input circuit by driving current through the CT secondary at levels approaching rated secondary current. (4) The 10-second maximum duration is sufficient for instantaneous trip testing and short-time thermal withstand verification. For continuous high-current testing, the standard 6-phase mode at 10A per phase provides 60A aggregate.
Q4: How does GPS synchronous triggering enable end-to-end line differential protection testing?
Line current differential protection (87L) compares currents measured simultaneously at both ends of a transmission line via fiber-optic communication. Testing this scheme traditionally required two test sets at opposite ends of the line, with test engineers coordinating by mobile phone—a process prone to timing errors and communication delays. GPS synchronization (available as an option on the XHJB666) equips both test sets with satellite-disciplined clocks accurate to ±1μs. The operator at each end pre-loads the same test sequence with a GPS-timed start trigger. Both test sets begin injecting synchronized fault currents simultaneously, creating the precise differential and through-current conditions needed to verify the 87L relay’s operating characteristic, restraint slope, and communication channel delay compensation. This capability is essential for commissioning modern digital substations where line differential is the primary protection scheme.
Q5: What protection functions and relay types can the XHJB666 test?
The XHJB666 supports comprehensive testing of virtually all protection functions found in modern substations: Overcurrent (50/51, 50N/51N, directional, voltage-controlled), distance (21, quadrilateral and mho characteristics, power swing blocking, teleprotection schemes), differential (87T transformer, 87B busbar, 87L line, 87G generator), voltage (27/59 under/over, 59N neutral displacement), frequency (81U/81O under/over frequency, ROCOF), synchronizing (25), breaker failure (50BF), auto-reclosing (79), and generator protection (40, 46, 32, 64S). Relay types include electromechanical, solid-state, and all generations of numerical/IED relays compliant with IEC 61850. The automated test software modules provide pre-configured test sequences for each protection function, while the fault playback capability reproduces COMTRADE-format disturbance records from actual system events for forensic analysis and protection setting validation.
Complete operation manual and test software documentation available — Contact us for technical consultation and on-site demonstration
Overall Rating
Rating Snapshot
The following is the distribution of all ratingsAll Reviews