ARC Cable Fault Locator XHGG502A
Description
XHGG502A ARC cable fault pre locator uses an industrial-grade 10.1-inch touch screen and a simple Windows operating system. It adopts industrial-grade integrated circuits and devices and has a built-in large-capacity lithium-ion battery. It is a special instrument for measuring and analyzing the status and fault distance of power cables. It is stable, reliable and easy to use.
It uses a combination of modern electronic technology and computer technology to implement signal filtering, acquisition, data processing, graphic display, and graphic analysis to complete cable speed measurement, cable length testing, and cable fault distance testing.
It is suitable for low-resistance, short-circuit, open-circuit and disconnection faults of power cables, high-frequency coaxial cables, street light cables, and buried wires made of various materials with different cross-sections and media, as well as high-resistance leakage and high-resistance flash over.
Main features
Technical Parameter
Item | Parameter |
Pre-location method | LV TDR (low voltage pulse method/ impulse reflection method) |
HV TDR(high voltage flash over method /single impulse method ) | |
ARC (multiple impulse arc reflection method) | |
ICE (impulse current method) DECAY (voltage decay method) |
|
Automatically test velocity speed | |
Display | 10.1 inch industrial-grade computer control, touch operation mode |
System | Windows operating, automatic generate test reports. |
Function | Speed, resistance, distance measurement |
Sampling frequency | 1MHz~400MHz |
Low voltage pulse amplitude | 300V±15% |
Pulse width | 0.15uS/0.30uS/0.60uS/1.20uS/2.4uS/5.0uS/7.5uS/10uS; |
Measuring distance | 100m/300m/500m/1km/3km/5km/10km/25km/50km/100km/120km |
Reading resolution | 0.07m; |
Test accuracy | ≤±(0.5%×L+1m), L is the cable length; |
Test blind zone | ≤10m; |
Power supply |
Charging AC110V~240V, 50Hz/60Hz Built-in 5200mAH lithium battery power supply; charging time of about 2 hours, working time of more than 5 hours |
Pulse coupler withstand voltage | DC 35kV |
Working conditions | Temperature -20℃~+65℃, relative humidity 90%, atmospheric pressure 750±30mmHg; |
Volume & Weight |
Cable fault tester: L358mm*W284mm*H168mm-4.7kg Pulse coupler: L430mm*W380mm*H220mm-10kg |