Underground power cables are the quiet workhorses of any electricity network. They run for kilometers under roads, pavements and fields, so when one of them fails, you cannot simply "look" for the problem. The cable is out of sight, and every minute of downtime costs money. The first question on site is always the same: where exactly is the fault?
The fastest way to answer that question is a technique called Time-Domain Reflectometry (TDR), also known in the industry as the "traveling wave method." This guide explains, in plain language that beginners can follow, how TDR works, how to read its waveforms correctly, and why an all-in-one instrument like the XHGG502A+ Cable Fault Pre-locator makes the whole job faster, easier and more reliable.
Think of TDR like shouting into a long tunnel. You shout at the entrance, and if the tunnel is clear, the sound simply travels away. But if there is a wall, a door, or a hole somewhere inside, part of your shout bounces back as an echo. The time it takes for the echo to return tells you roughly how far away the obstruction is.
A cable fault locator works the same way, but with an electrical pulse instead of sound. It fires a short pulse into the cable. Wherever the cable’s impedance changes — at a fault, a joint, or the open end of the cable — a small part of the pulse is reflected back to the instrument. By measuring the time delay between the outgoing pulse and the returning echo, the instrument calculates the distance to that point. The basic formula is simple:
The division by two is needed because the pulse travels to the fault and then all the way back — it covers the distance twice.
Two useful facts make waveform reading easy to learn. First, the polarity of the echo tells you what kind of point the pulse has hit. A reflection from an open circuit (or the cable terminal) comes back with the same polarity as the outgoing pulse, while a reflection from a short circuit or a low-impedance fault comes back inverted. Second, TDR gives you a rough, or "pre-located," distance. After TDR narrows the search down to a short section of cable, you still do precise pinpointing on the spot with an acoustic-magnetic device to find the exact point before digging.
Before touching the instrument, it helps to understand the four main types of cable fault, because each one needs a different test method:
In practice, you first judge the nature of the fault — for example by measuring insulation resistance with a megohmmeter — and then choose the matching test mode. This is exactly the workflow a full-featured locator like the XHGG502A+ is designed to support.
The most important habit to build is checking polarity. If the returning echo has the same polarity as the outgoing pulse, it came from an open circuit or the cable terminal. If the echo is inverted (opposite polarity), it came from a short circuit or a low-impedance fault. This single rule lets you identify the fault nature at a glance.
On the screen you see the outgoing pulse at time t1, then a reflected pulse at time t3 that has the same polarity as t1 (a positive echo). Between them, a small same-polarity echo at t2 is the reflection from an intermediate joint. At t4 you see a secondary reflection from the fault, smaller than the primary one because the pulse loses energy on its way. The fault distance is measured from t1 to t3. On the XHGG502A+, you simply move the cursor to these two points and the instrument shows the calculated distance automatically.
Here the story is almost the same, except that the echo at t3 has the opposite polarity to the outgoing pulse. There may also be a reflection from the cable terminal further along. Once you see an inverted echo, you know the fault is a low-resistance or short-circuit type and you can read the distance the same way.
Intermediate joints and connectors also reflect the pulse, and their echo is usually of the same polarity (though this depends on the connector structure). A beginner can easily mistake a joint reflection for a real fault. The trick is to save a reference waveform of the healthy, full-length cable. Comparing the fault waveform against the reference makes the real fault echo stand out clearly.
When testing high-resistance faults with the high-voltage flashover method, the waveform begins with a spark-gap discharge at t0, followed by the primary reflected wave from the fault at t1 and the secondary reflection at t2. Measure the distance from the test end to the fault point as usual.
One special case is a fault very close to the test end. The waveform then shows a series of reflected waves that look like a decaying cosine oscillation. Instead of measuring one single echo, you take several periods, measure the distance across them, and divide by the number of rising and falling edges to get the average. This is a small detail, but it prevents big errors in near-end faults — the area inside the instrument’s test blind zone (for the XHGG502A+, about 10 m).
The XHGG502A+ integrates three TDR test methods plus a built-in megohmmeter, so one instrument covers virtually every power cable fault you are likely to meet.
This method sends a low-voltage pulse (300 V ± 15%) into the cable and is ideal for open-circuit, low-resistance and short-circuit faults. It is the fastest and simplest method, and it is also the one you use to measure cable length and to calibrate wave velocity.
For leakage and flashover high-resistance faults, the low-voltage pulse cannot "see" the fault directly. The XHGG502A+ therefore uses the high-voltage flashover method, which comes in two forms. Direct flashover uses a DC high-voltage supply to force a flashover discharge at the fault; impulse flashover (also called the universal method) uses a high-voltage pulse signal source. In both cases the reflected signal is picked up by a dedicated sampler and fed into the tester for analysis.
The most challenging faults are high-resistance faults that need high voltage. Right at the moment of the impulse, the cable can be swamped by a large cosine oscillation that hides the useful echo. The multiple pulse method solves this elegantly: after the high-voltage unit breaks down the fault point, a trigger device immediately fires several low-voltage test pulses. While the arc is still conducting, these pulses see a short-circuit-like echo and form eight fault-reflection pulses; after the arc goes out, eight more pulses are sent to record the open-circuit reflection. The result is eight sets of clean, high/low-voltage comparison waveforms. Among them you will almost always find a set that is easy to read, and the XHGG502A+ displays these 1–8 groups for automatic or manual distance measurement.
![]()
Here is a simple routine that works for most jobs. It follows the workflow recommended in the XHGG502A+ manual.
A practical tip from the manual: on long or unknown cables, first use the low-voltage pulse method to measure the full length of every phase and calibrate the wave velocity. Then run the actual fault test. This one habit removes the most common source of distance error.
For maintenance teams who want one instrument that covers the whole job — not a drawer full of separate boxes — the XHGG502A+ is designed around two ideas: comprehensive and convenient.
Reading TDR waveforms is not magic. Once you understand the polarity rule, learn to measure from the leading edges, and learn to separate joint echoes and oscillations from the real fault, you can locate cable faults quickly and confidently. Choosing the right instrument makes that learning curve far shorter.
The XHGG502A+ Cable Fault Pre-locator brings low-voltage pulse, high-voltage flashover and multiple pulse testing together with a built-in megohmmeter in a single rugged, easy-to-use package. Its comprehensive modes, automatic analysis and clear waveform display help your team find faults faster — with less training and fewer mistakes. For any team that works on underground power cables, it is the all-in-one, convenient choice.