2026-09-04
ISTANBUL, Turkey — A 10 kV underground cable fault location project was recently completed in Istanbul, Turkey, by our cable fault detection team. By combining insulation resistance testing, the low-voltage pulse method and the high-voltage flashover method, engineers pinpointed a leakage-type low-resistance fault at 172 m along a 177 m YJV cable, providing the local utility operator with an accurate excavation reference and reducing outage time to a minimum.
The target line was a 10 kV medium-voltage distribution cable serving an industrial area in Istanbul. The operator reported a ground fault that tripped the feeder, and the cable was isolated for diagnosis. The key project information is summarized below:
| Project | 10 kV cable fault detection, Istanbul, Turkey |
| Cable model | YJV-8.7/10 kV, 3×240 mm² |
| Cable length | 177 m (measured by low-voltage pulse method on all phases) |
| Fault nature | Leakage-type low-resistance fault |
| Measured fault distance | 172 m (high-voltage flashover method at 28 kV) |
Using an insulation resistance tester on the 2500 V range, the team measured the resistance of each phase to ground: A-phase 0.03 MΩ (169 V), B-phase 0.04 MΩ (155 V) and C-phase 0.01 MΩ (146 V). The extremely low readings on all three phases indicated a leakage-type low-resistance fault rather than a high-resistance breakdown, and guided the selection of the most suitable fault location methods.
The low-voltage pulse method was then applied to measure the cable and evaluate the fault condition. The instrument returned a cable length of 177 m for the C phase, with the other phases also measuring 177 m. The fact that the fault distance could be read directly by the low-voltage pulse method confirmed that the resistance at the fault point had already dropped to an extremely low level.
To verify the fault distance precisely, the team switched to the high-voltage flashover method. The test voltage was raised to 28 kV, and the fault point was measured at 172 m — just 5 m short of the far cable end. Waveform analysis showed a clear flashover at the fault location, giving the on-site crew an accurate and reliable digging point.
This project once again demonstrates the efficiency of combining insulation resistance testing, low-voltage pulse ranging and high-voltage flashover verification for 10 kV cable fault location. With professional cable fault locators and experienced on-site engineers, our team helps utility and industrial customers in Turkey and beyond restore power quickly and reduce the economic losses caused by prolonged outages.