| General features | |
|---|---|
| Portable cable fault location system | |
| Graphical interface | Graphical interface, more intuitive and easy to operate. |
| Operation | Turn and click a single knob (jog dial) on the control unit |
| Data management | General database |
| Data Synchronization | Universal Serial Bus |
| Control unit | |
| Display | Industrial grade TFT color panel with LED backlight |
| Anti-glare | have |
| Multi-touch | have |
| LCD size | 10" |
| Aspect Ratio | 16:9 |
| Resolution | 1024 x 768 Full HD |
| Brightness | 450 cd/m² |
| Safety | |
| Adaptability | CE Compliance;EN 61010,EN 50191,VDE 0104,VDE 015,DGUV 203-034(BGI 891) |
| Discharge and grounding devices | 72kJ, equivalent to the energy stored in a 10µF capacitor charged to 120kV DC fast charge: discharge time constant < 1 second |
| System Status | Real-time monitoring and indication |
| Intrinsically safe | Ground immediately when there is a power outage |
| F-U safety interlock | Operating voltage connection monitoring (high voltage circuit) |
| F-Ohm Safety Interlock | Operational earth connection monitoring (high voltage circuit) |
| Security Features | Front panel: power on/off, lockout button switch, emergency stop, residual pressure indicator light, high voltage switch; Control unit: Knob (jog dial) |
| Safety devices | System grounding status indicator, power input protection device, high voltage room monitoring through door contact, external safety device |
| Power input monitoring | Overvoltage protection, undervoltage protection, residual current device (RCD) |
| Defining Wiring | There is a switchboard inside the system |
| System function | |
|---|---|
|
1.Use DC or high-voltage pulse to make the cable fault point flash over and discharge 2.Use the traveling wave reflection principle to make a rough measurement of all types of cable main insulation faults |
|
| I,High voltage surge generator | |
| Output mode | DC, Single, Cycle |
| Output voltage | 8kV,16kV,32kV |
| Built-in capacitor | 64uF,16uF,4uF |
| Discharge energy | 2048J @ each voltage level |
| Impact power | 2000VA |
| Impulse rate | Automatic impact for about 6 seconds, manual impact for any control time |
| Surge voltage levels switch | Manual |
| Voltage adjustment type | Continuous |
| Indication | High-voltage side voltage metering, indication of output voltage and current in real time |
| Operating modes switch | Manual |
| Coupler | Built-in multiple pulse sampling box |
| Safe protection | With zero start protection function, safe and reliable |
| Discharge | Unique high-voltage measurement design, in the stop state, it will automatically discharge the internal capacitance of the device |
| Working power | AC 220V±15% ,50Hz±2Hz(60Hz) |
| DC withstand voltage testing | Output voltage adjustable and indication range 0-32kV, output current indication range 0-20A |
| Burn current |
Fault conditioning (burning) with current up to 60 mA @ 32 kV, 120 mA @ 16kV, 240mA@8kV |
| Safety |
Over-voltage, Over-current, Overheating protection. Automatic discharge after operation |
| Protection rating | Not lower than IP54 |
| Dimensions(mm) | 534L*444W*805H mm |
| Total weight | Not more than 130kg |
| II,TDR cable fault locator | |
| Test method | Low voltage pulse, Impulse current, Impulse voltage, ARC multipls pulse |
| Sampling rate | 1MHz~400MHz |
| Pulse output | Unipolar |
| Pulse Amplitude | 300V |
| Pulse width | 0.15μS/0.30μS /0.60μS/1.20μS/2.4μS/5.0μS/7.5μS/10μS |
| Measurement scope | ≥120km |
| Measurement range | 100m/300m/500m/1km/3km/5km/10km/25km/50km/100km |
| Minimum resolution | 0.07m |
| Measurement error | ≤±(0.5%*L+1m),L is cable length |
| Signal gain | 0…100%,adjustable |
| Propagation speed | 10…999.9m/µs |
| Output Impedance | Automatic match |
| Trigger |
Automatic continute |
| Result analysis | Automatic measure fault distance |
| Working conditions | temperature -25℃~+65℃, relative humidity 85%, atmospheric pressure 750±30mmHg |
| V Test cables | |
|
(Note: Due to the existence of 35kV high voltage, special high voltage cables are made and should be kept away from the site during operation.) |
|
| High voltage output cable | core wire 2.5mm2 red, withstand voltage 50kV DC, with shielding layer, outer diameter 14mm, length can be customized according to customer’s requirements, including installation of large spool. |
| Ground cable | grounding 3-column - main core 16mm2 transparent color, branch 2.5mm2, length can be customized according to customer’s requirements, including installation of small spool. |
This device can use the multiple pulse method to measure distance, and only one short-circuit wire is needed. In addition, when accurately locating the cable fault, it can also be switched to the high-voltage flash-over method (pulse current method - ICE), just remove the short-circuit wire and insert the high-voltage output cable into another HV output port. This ensures high energy output during accurate locating, and will not reduce part of the energy due to the multiple pulse coupler, resulting in less clear sound when listening to the fault discharge sound.