The XHDD503B HV Cable Fault Pinpointer is engineered for high-voltage cable fault location in demanding field environments. It employs synchronous acoustic-magnetic pinpointing and identification technology to precisely locate underground cable faults. The instrument completes precise fault positioning within rough measurement ranges, collects acoustic-magnetic signal time differences (up to 80ms), and integrates positioning technology with path-assisted testing. Multiple test modes with comprehensive diagnostic prompts ensure efficient, accurate fault location for professional HV field operations.
![]()
HV Field Reliability
Accuracy: 0.1m | Time Difference: 80ms max | Battery: 8.4V 2.4Ah Li-ion | Runtime: 8+ hours | Charge: <3h | Altitude: <4500m
| Parameter | Specification |
|---|---|
| Sound Channel Filter | All-pass: 100~1500Hz / Low-pass: 100~400Hz / High-pass: 150~1500Hz / Band-pass: 200~600Hz |
| Sound Channel Max Gain | ≥100dB |
| Magnetic Channel Max Gain | ≥100dB |
| Signal Gain Adjustable | 1 to 8 levels (acoustic & magnetic) |
| Trigger Threshold | 0 to 99 levels adjustable |
| Acoustic-Magnetic Time Difference | Up to 80ms (auto-calc + manual analysis) |
| Positioning Accuracy | 0.1m |
| Display | 5-inch color LCD, 854x480, touch function |
| Battery | Built-in Li-ion, 8.4V, 2.4Ah |
| Continuous Operation | > 8 hours |
| Charger | Input: AC220V±10%, 50Hz; Output: 8.4V, 1A |
| Charging Time | < 3 hours |
| Operating Temperature | -20 ~ 65°C |
| Humidity | ≤90% RH |
| Maximum Altitude | < 4500m |
The instrument uses synchronous acoustic-magnetic positioning: an impact discharge generator creates flashover at the cable fault point, and the dedicated dual-channel probe simultaneously captures both acoustic and electromagnetic signals. Because the magnetic signal propagates near-instantaneously while sound travels considerably slower, the time difference between the two signals directly correlates to the distance from the fault point. The instrument's waveform display shows both signals in real time, with automatic time difference calculation (0-80ms range). By moving the sensor along the cable path and finding the point with the minimum time difference, the exact fault location is identified at 0.1m precision — far more reliable than traditional acoustic-only methods that rely solely on operator hearing.
| Component | Quantity |
|---|---|
| HV Cable Fault Pinpointer (Main Unit) | 1 |
| Probe with Sensor and Connecting Rod | 1 |
| 7-Core Signal Cable | 1 |
| Headphones | 1 |
| Fast Charger (AC220V / 8.4V 1A) | 1 |
After-Sales: 12-month warranty, lifetime technical support. Rated for field operations up to 4500m altitude.