The XHDD503B is a digital acoustic-magnetic synchronous cable fault pinpointer engineered for power cable fault emergency repair operations. Designed to operate in conjunction with a high-voltage signal generator, this portable intelligent device integrates acoustic-magnetic time difference positioning technology, BNR background noise reduction, and path auxiliary detection into a single 7kg field unit.
With a maximum signal gain of 100dB and 0.1m fixed-point accuracy, the XHDD503B delivers precise fault location across multiple test modes. The 5-inch color touch LCD (854×480 resolution) provides clear real-time waveform display with automatic acoustic-magnetic time difference calculation up to 80ms. Bar graph indicators for both sound and electromagnetic signal strength, combined with adjustable trigger thresholds, enable operators to efficiently and accurately complete cable fault pinpointing in demanding field conditions.
| Acoustic-Magnetic Synchronization Performance | |
|---|---|
| Sound Channel Bandwidth (All-pass) | 100Hz ~ 1500Hz |
| Low-pass Filter | 100Hz ~ 400Hz |
| High-pass Filter | 150Hz ~ 1500Hz |
| Band-pass Filter | 200Hz ~ 600Hz |
| Maximum Signal Gain | ≥100dB |
| Fixed Point Accuracy | 0.1m |
| Acoustic-Magnetic Time Difference Range | Max 80ms |
| BNR Noise Reduction | Supported |
| Display & Control | |
| Display Type | 5-inch Color LCD Touch Screen |
| Resolution | 854 × 480 |
| Sound Signal Indication | Bar Graph with Adjustable Trigger Threshold |
| Electromagnetic Signal Indication | Bar Graph with Adjustable Trigger Threshold |
| Power & Physical | |
| Battery | 8.4V 2.4Ah Lithium-Ion Pack |
| Continuous Operation | > 8 Hours |
| Charger Input | AC 220V ±10% / 50Hz |
| Charger Output | 8.4V / 1A |
| Charging Time | < 6 Hours |
| Weight | 7 kg |
| Environmental | |
| Operating Temperature | -10℃ ~ 55℃ |
| Relative Humidity | 5% ~ 90% RH |
| Altitude | < 4500m |
When the high-voltage signal generator applies impulse voltage to the fault cable, discharge at the fault point generates both acoustic and electromagnetic signals. The electromagnetic signal propagates at near light speed, while the acoustic signal travels at approximately 340m/s through soil. The XHDD503B measures the time difference between these two signal arrivals. As the operator moves the sensor along the cable path, the point with the minimum acoustic-magnetic time difference indicates the exact fault location directly below. The system supports both automatic calculation and manual waveform analysis, with a maximum measurable time difference of 80ms.
BNR Background Noise ReductionField environments often present high levels of ambient noise from traffic, machinery, and weather conditions. The XHDD503B's BNR (Background Noise Reduction) mode employs advanced digital filtering to isolate the characteristic discharge sound from background noise, significantly improving the signal-to-noise ratio. Combined with the adjustable sound trigger threshold, operators can precisely tune the detection sensitivity to match field conditions.
Application ScenariosOperational Note: The XHDD503B is designed for use with a compatible high-voltage signal generator. For optimal results, ensure proper grounding and follow the instrument operating procedures detailed in the user manual. The built-in lithium battery should be charged every 2 months during extended storage periods to maintain battery health.