logo
Home > Products >
Circuit Breaker Analyzer
>
Surge Arrester Monitor Calibrator 1000kV Class DC Monitor 0-30mA 55Hz Output 0.001mA Resolution | XHJS401A

Surge Arrester Monitor Calibrator 1000kV Class DC Monitor 0-30mA 55Hz Output 0.001mA Resolution | XHJS401A

Product Details:
Place of Origin: Xi'an Shaanxi China
Brand Name: XZH TEST
Certification: ISO CE
Model Number: XHJS401A
Detail Information
Place of Origin:
Xi'an Shaanxi China
Brand Name:
XZH TEST
Certification:
ISO CE
Model Number:
XHJS401A
Highlight:

High Light

Highlight:

Surge Arrester Monitor Calibrator 1000kV Class

,

DC Arrester Monitor Calibration Tester

,

Arrester Monitor Counter Verifier 0.001mA

Trading Information
Minimum Order Quantity:
1 unit
Price:
Negotiable
Packaging Details:
wooden packaging
Delivery Time:
5-8 work days
Payment Terms:
T/T
Supply Ability:
3000unit/year
Product Description
Product Overview

The Surge Arrester Monitor Calibrator is designed specifically to cater to the requirements of DC-type arrester monitors (e.g., Model JCQ(WZ)-16) in power systems. This equipment is primarily applied to calibrate arrester monitors of the 1000kV class, ensuring that the on-line leakage current readings and action counter records provided by the monitors are accurate and trustworthy. Regular calibration of arrester monitors is an important part of preventive maintenance, because an inaccurate monitor may fail to reflect the real condition of the zinc oxide arrester and can delay the discovery of internal defects before the thunderstorm season.

Target Users

This calibrator is designed for electrical teams of dairy and livestock farming facilities, which protect milking, feeding and ventilation systems with arresters and need dependable monitor accuracy; primary and secondary school campus facility engineering teams, which maintain campus distribution networks and lightning protection systems with limited technical staff; supermarket and retail chain store facility management teams, which require quick on-site verification of monitors protecting refrigeration and HVAC equipment; and swimming pool, spa and sports club facility engineering teams, which rely on accurate arrester monitoring for outdoor lighting and water treatment systems.

Performance Features
The measured values demonstrate excellent stability, giving repeatable and reliable calibration results;
In the online state, the heterodyne output possesses high anti-interference performance against the live system;
It outputs standard sine waves, which closely match the actual leakage current waveform of the arrester;
Equipped with a built-in battery for measurement, it facilitates easy on-site operation without external power;
Output current ranges of 0-5mA, 10mA and 30mA are customizable for monitors of different rated currents;
Cyclic measurement with 1-2 seconds per action enables continuous verification of the monitor action counter.
Technical Specifications
Item Specification
Power supply Built-in 10.4Ah 12V battery
Output frequency 55Hz
Output current 0-5mA / 10mA / 30mA (customizable)
Resolution 0.001mA
Current accuracy 0.5% ± 3 digits
Inrush current 50A ~ 100A (instantaneous)
Inrush voltage DC 1500V / 1800V
Action count 1 ~ 2s per time
Number of actions Cyclic measurement
Calibration Procedure and On-Site Application Notes

To calibrate an on-line arrester monitor, the operator connects the calibrator to the current loop of the monitor and selects the output current range matching the monitor rating, from 0-5mA up to 30mA. The calibrator then injects a standard 55Hz sine wave signal, and the value shown on the monitor is compared with the known output to verify measurement accuracy. For the action counter, an instantaneous inrush current of 50A to 100A together with a DC inrush voltage of 1500V or 1800V is applied to trigger the counting mechanism, and the action count is checked in a cyclic rhythm of 1-2 seconds per action. Because the whole process runs on the built-in battery, the calibration can be performed directly at the installation site, which is especially valuable for 1000kV-class monitors distributed across wide substation and plant areas before the annual thunderstorm season.

Surge Arrester Monitor Calibrator
FAQ
Q1: Why do surge arrester monitors need regular calibration?

On-line monitors can drift in accuracy over long service periods, and an inaccurate monitor may fail to reflect the real condition of the arrester. Regular calibration ensures the leakage current readings and action counts are reliable before each thunderstorm season.

Q2: What types of arrester monitors can this calibrator handle?

It is designed for DC-type arrester monitors such as the Model JCQ(WZ)-16 series, primarily for the calibration of 1000kV-class arrester monitors, with customizable output current ranges of 0-5mA, 10mA and 30mA.

Q3: How does it verify the action counter of the monitor?

The calibrator generates an instantaneous inrush current of 50A to 100A together with a DC inrush voltage of 1500V or 1800V to trigger the counting mechanism, and verifies the action count in a cyclic mode of 1-2 seconds per action.

Q4: Can calibration be performed while the monitor is online?

Yes. In the online state, the heterodyne output possesses high anti-interference performance, so the calibration can be carried out reliably without disconnecting the monitor from the live system.

Q5: Is the instrument convenient for field use?

It is equipped with a built-in 10.4Ah 12V battery, and outputs a standard 55Hz sine wave with a current accuracy of 0.5% plus or minus 3 digits and a resolution of 0.001mA, making it easy to operate at the installation site.