Output Time:
0~5A Continuous / 5~10A ≥45 Seconds / 10~20A ≥5 Seconds
Highlight:

High Light

Highlight:

High Performance Relay Test Kit

,

6 Phase Relay Protection Tester

,

Secondary Injection Microcomputer Relay Tester

Trading Information
Minimum Order Quantity:
1set
Packaging Details:
wooden packaging
Delivery Time:
5-8 work days
Payment Terms:
T/T
Supply Ability:
3000unit/year
Product Description

Product Overview


XHJB666 Microcomputer Relay Protection Calibrator is a compact microcomputer-based relay protection testing instrument adopting microelectronic technology. Complying with DL/T624-2010 standard for relay protection microcomputer test devices, it is optimized by analyzing the pros and cons of conventional peer products.

Performance Features


Equipped with a high-performance industrial PC, high-speed DSP, 16-bit DAC module, 8.4-inch LCD screen and embedded keyboard in the main unit. The device is operable independently or via laptop connection, boasting robust functions, small footprint and superior testing precision.

High Performance 6 Phase Relay Test Kit with Secondary Injection for Relay Protection Testing 0

Technical Parameters

★ AC Current Source: Single Phase: 6×30A Three Phase: 180A Power: ≥250VA/phase

★ Output Time: 0~5A continuous / 5~10A ≥45 seconds / 10~20A ≥5 seconds

★ AC Voltage Source: Single Phase: 6×120V Output Power: ≥60VA/phase

★ DC Current Source: Single Phase: -5A~+5A Power: ≥100VA

★ DC Voltage Source: Single Phase: -150V~+150V Power: ≥100VA

★ AC Source Angle: Phase Angle: 0°~360° Accuracy: ±0.5°

★ AC Source Frequency: Frequency: 1~1000Hz Frequency Resolution: 1mHz

★ Harmonic Output: Capable of outputting harmonics of any amplitude from the 2nd to the 20th order

★ Synchronization: Voltage and current synchronization ≤10μS

★ Input: 16 channels compatible with 15V~250V active contacts, automatic contact polarity identification

★ Timing accuracy: ≤1ms when less than 1s

★ Output: 8 pairs of programmable switch dry contacts, capacity: AC/DC 250V, 0.5A

★ Power supply: 220V±10% 50Hz±10%