Transformer Tester
>
On-Load Tap Switch Tester Action Sequence Switching Time Three-Phase Synchronization for Preventive Transformer Testing

On-Load Tap Switch Tester Action Sequence Switching Time Three-Phase Synchronization for Preventive Transformer Testing

Product Details:
Place of Origin: Xi'an, Shaanxi, China
Brand Name: XZH TEST
Certification: CE, ISO
Model Number: XHYZ1668
Detail Information
Place of Origin:
Xi'an, Shaanxi, China
Brand Name:
XZH TEST
Certification:
CE, ISO
Model Number:
XHYZ1668
Model NO.:
XHYZ1668
Power:
Electricity
Customized:
Customized
Color:
Yellow
Output Current:
1A, 0.5A, 0.2A
AC On-Load:
Customized
Transport Package:
Exported Wooden Case
Trademark:
XZH TEST
Supply Ability:
2000PCS/Year
Customization:
Available
Warranty:
12 Months
Highlight:

High Light

Highlight:

on-load tap switch tester

,

switching time synchronization analyzer

,

preventive transformer maintenance tester

Trading Information
Minimum Order Quantity:
1 unit
Price:
Negotiable
Packaging Details:
wooden case
Delivery Time:
5-8 days
Payment Terms:
T/T
Supply Ability:
2000unit/year
Product Description
On-Load Tap Switch Tester|XHYZ1668
Introduction

The on-load tap changer is the only moving part connected to the transformer circuit, so its detection is increasingly important. According to the procedures for handover and preventive tests of electrical equipment, the action sequence and switching time of the on-load tap changer must be checked. The XHYZ1668 On-Load Tap Switch Tester measures the transition waveform, transition time, instantaneous transition resistance and three-phase synchronization. It is highly intelligent with intuitive on-screen prompts, compact, lightweight and strongly anti-interference, greatly reducing field workload, and is an ideal instrument for power generation and supply units and the transformer manufacturing industry.

Key Features
  • Large output current with light weight.
  • Tests YN, Y and delta transformers with resistance values displayed directly without conversion.
  • Supports measurement both with and without winding.
  • Waveform display automatically adjusts resistance and time amplitude based on sampling values.
  • Complete protection circuit for strong reliability.
  • 7-inch large LCD display for convenient field operation.
  • Internal storage of 500 groups of data.
Technical Specifications
Output current 1.0A, 0.5A, 0.2A
Transition resistance range 0.3Ω ~ 20Ω (1.0A)
5Ω ~ 40Ω (0.5A)
20Ω ~ 100Ω (0.2A)
Transition time 0 ~ 320 ms
Open circuit voltage 24 V
Measurement accuracy Transition resistance: ±(5% reading ±0.1Ω)
Transition time: ±(0.1% reading ±0.2 ms)
Sampling rate 20 kHz
Storage Local storage (500 groups)
Dimensions Host: 360 × 290 × 170 mm
Cable box: 360 × 290 × 170 mm
Weight Host: 6.15 kg
Cable box: 4.55 kg
Ambient temperature -10ºC ~ 50ºC
Ambient humidity ≤ 85% RH
Working power supply AC220V ±10%
Power frequency 50 ±1 Hz
Who Is It For

Built for routine and commissioning use in the field, the XHYZ1668 serves the maintenance and handover-testing teams that keep transformer fleets in service:

  • Substation and power plant electrical maintenance departments performing routine preventive tests.
  • Commissioning engineers conducting handover tests on newly installed transformers.
  • Utility field service crews carrying out periodic on-load tap changer inspections.
  • Electrical contractors and service providers managing transformer O&M programs.
Product Details

On-Load Tap Switch Tester Action Sequence Switching Time Three-Phase Synchronization for Preventive Transformer Testing

FAQ
1. Who should use this tap switch tester?
It is built for substation and power plant maintenance teams, commissioning engineers performing handover tests on newly installed transformers, and utility field service crews running routine preventive tests.
2. What does it verify during preventive and handover tests?
It measures the tap changer action sequence, switching time, transition waveform, transition resistance and three-phase synchronization, meeting preventive test procedure requirements.
3. Is it practical for routine on-site maintenance?
Yes. Its compact size, light weight, strong anti-interference and 7-inch LCD display make it convenient for field crews performing periodic on-load tap changer inspections.
4. Does it confirm three-phase synchronization?
Yes. It measures three-phase consistency so engineers can quickly verify that all three phases switch in sync and detect any timing deviation.
5. How does it support maintenance record-keeping?
It automatically stores 500 groups of data internally, supporting paperless records for maintenance archives and periodic comparison.