AC current output | output precision | class 0.2 |
Phase current output (RMS) | 0~40A | |
Three parallel current output (RMS) | 0~120A | |
Phase current allowable working value for a long time (effective value) | 10A | |
Phase current maximum output power | 420VA | |
The maximum output power | 900VA when the three-parallel current is at the maximum output | |
When the maximum output of three parallel currents is allowed to work, the working time is 10s | ||
Frequency range (fundamental wave) | 20~1000Hz | |
Harmonic times | 1-20 times | |
DC current output | Output accuracy | class 0.2 |
Current output | 0~±10A / each phase, 0~±30A / three parallel | |
Maximum output load voltage | 20V | |
AC voltage output | Output accuracy | class 0.2 |
Phase voltage output (effective value) | 0~120V | |
Line voltage output (effective value) | 0~240V | |
Phase voltage/line voltage output power | 80VA / 100VA | |
Frequency range (fundamental wave) | 20~1000Hz | |
Harmonic times | 1-20 times | |
DC voltage output | Output accuracy | class 0.2 |
Phase voltage output amplitude | 0~±160V | |
Line voltage output amplitude | 0~±320V | |
Phase voltage/Line voltage output power | 70VA / 140VA |