| Screen size | 7-inch |
| Power supply method | Charging AC110V~240V, 50Hz/60Hz;Powered by built-in 10400mAh lithium battery |
| Working conditions | -20~+65℃, relative humidity ≤90% |
![]()
Regarding waveforms
Standard waveforms for the entire length and intermediate joints
![]()
Analysis: At time t1, the pulse waveform generated by the flash detector is positive (or negative); at time t2, the back pulse waveform from the intermediate joint in the cable is shown; at time t3, the full-length (terminal) reflected pulse waveform is positive, representing a reflection of the same polarity (similar to an open circuit fault); at time t4, the full-length (terminal) secondary reflected waveform is shown. Due to pulse attenuation, the secondary reflected pulse waveform at time t4 has a smaller amplitude than the primary reflected pulse waveform at time t3. The total length of the cable and the distance between the intermediate joints are also considered.
![]()