The XHDJ706 is a digital earth resistance and soil resistivity tester for grounding acceptance work. It measures ground resistance from 0.00 Ω to 30.00 kΩ, soil resistivity from 0.00 Ωm to 9999 kΩm, and ground voltage from 0.00 V to 600 V AC.
The tester uses a four-wire, three-wire or simple two-wire connection. In four-wire mode the ES auxiliary ground is clamped to the same point as E, which removes the effect of contact resistance at the ground body, auxiliary rod, test clip and instrument terminal, as well as the effect of test-lead resistance.
Built for grounding contractors and electrical teams that need one meter for both ground resistance and soil resistivity acceptance tests.
| Range | Accuracy | Resolution | |
|---|---|---|---|
| Ground resistance (R) | 0.00 Ω – 30.00 Ω | ±2 % rdg ± 5 dgt | 0.01 Ω |
| Ground resistance (R) | 30.0 Ω – 300.0 Ω | ±2 % rdg ± 3 dgt | 0.1 Ω |
| Ground resistance (R) | 300 Ω – 3000 Ω | ±2 % rdg ± 3 dgt | 1 Ω |
| Ground resistance (R) | 3.00 kΩ – 30.00 kΩ | ±2 % rdg ± 3 dgt | 10 Ω |
| Soil resistivity (ρ) | 0.00 Ωm – 99.99 Ωm | ρ = 2πaR | 0.01 Ωm |
| Soil resistivity (ρ) | 100.0 Ωm – 999.9 Ωm | ρ = 2πaR | 0.1 Ωm |
| Soil resistivity (ρ) | 1000 Ωm – 9999 Ωm | ρ = 2πaR | 1 Ωm |
| Soil resistivity (ρ) | 10.00 kΩm – 99.99 kΩm | ρ = 2πaR | 10 Ωm |
| Soil resistivity (ρ) | 100.0 kΩm – 999.9 kΩm | ρ = 2πaR | 100 Ωm |
| Soil resistivity (ρ) | 1000 kΩm – 9999 kΩm | ρ = 2πaR | 1 kΩm |
| Ground voltage | AC 0.00 V – 600 V | ±2 % rdg ± 3 dgt | 0.01 V |
| Parameter | Specification |
|---|---|
| Function | Two-wire, three-wire and four-wire ground resistance; soil resistivity; ground voltage |
| Ground resistance range | 0.00 Ω – 30.00 kΩ, automatic range shift |
| Soil resistivity range | 0.00 Ωm – 9999 kΩm, automatic range shift |
| Ground voltage range | AC 0.00 V – 600 V |
| Measurement method | Ground resistance: rated current change-pole method; soil resistivity: four-pole Wenner method; ground voltage: average rectification |
| Test frequency | 128 Hz |
| Short-circuit test current | AC > 20 mA, sine wave |
| Open-circuit test voltage | AC 28 V max |
| Electrode spacing | 1 m – 100 m, settable |
| Display | 4-digit large LCD, 111 mm × 68 mm; display field 108 mm × 65 mm; off-white backlight |
| Data storage | 500 groups; MEM storage indication; FULL symbol when full |
| Power supply | 6 × 1.5 V LR14 alkaline batteries (9 V); continuous standby > 100 hours |
| Automatic shut-down | APO indication; auto power-off after 15 minutes |
| Dimensions | 240 mm (L) × 188 mm (W) × 85 mm (H) |
| Weight | Instrument 1280 g including battery; test line 1300 g; auxiliary ground rods 720 g (4 pieces) |
| Operating conditions | -10 °C – 40 °C; < 80 % RH |
| Storage conditions | -20 °C – 60 °C; < 70 % RH |
| Overload protection | Ground resistance: AC 280 V / 3 s between H-E and S-ES ports |
| Insulation resistance | ≥ 20 MΩ at 500 V between circuit and case |
| Withstand voltage | AC 3700 V/rms between circuit and case |
| Standards | IEC61010-1 (CAT III 300 V, CAT IV 150 V, pollution degree 2); IEC61010-031; IEC61557-1; IEC61557-5; JJG 366-2004; IEC61326 (EMC) |