logo
Home > Products >
Ground Tester
>
Substation Ground Grid Tester XHEP701A 2000 Ohm Soil Resistivity 5A Output

Substation Ground Grid Tester XHEP701A 2000 Ohm Soil Resistivity 5A Output

Product Details:
Place of Origin: Xi'an Shaanxi China
Brand Name: XZH TEST
Certification: ISO CE
Model Number: XHEP701A
Detail Information
Place of Origin:
Xi'an Shaanxi China
Brand Name:
XZH TEST
Certification:
ISO CE
Model Number:
XHEP701A
Voltage:
0~400V±2%+0.005V
Maximum Resolution:
0.001V
Highlight:

High Light

Highlight:

Different Frequency Ground Tester

,

High Precision Earth Resistance Tester

,

Portable Ground Grid Resistance Tester

Trading Information
Minimum Order Quantity:
1set
Packaging Details:
wooden packaging
Delivery Time:
5-8 work days
Payment Terms:
T/T
Supply Ability:
3000unit/year
Product Description
XHEP701A · DIGITAL GROUND GRID TESTER
Substation Ground Grid Tester XHEP701A 2000 Ohm Soil Resistivity 5A Output
0.030 Ω – 2000 Ω
7-inch touch screen
1 – 5 A output
100 data groups

The XHEP701A digital large ground grid grounding resistance tester uses a variable-frequency AC power supply, dual-frequency measurement, a 7-inch touch colour screen and microprocessor control. It performs two-wire, three-wire and four-wire impedance tests and also measures soil resistivity, step voltage, distribution potential, contact voltage and impedance angle.

The output has a maximum open-circuit voltage of 400 V and a maximum short-circuit current of 5 A. Microprocessor control and automatic dual-frequency measurement calculate the 50 Hz power-frequency grounding impedance under strong interference. The meter stores 100 groups and has a built-in thermal printer.

Product View
Substation Ground Grid Tester XHEP701A 2000 Ohm Soil Resistivity 5A Output
Who This Tester Is For

For substation and power distribution grounding teams that need acceptance and periodic impedance checks on large grounding grids.

Substation grounding teams checking grounding impedance and contact voltage before acceptance, after grid expansion and during periodic maintenance.
Power distribution and tower-line crews measuring grounding impedance, soil resistivity and step voltage along distribution lines and tower transmission lines.
Factory electrical teams verifying factory grounding grids and lightning rods, where both impedance and soil resistivity data are required.
Key Capabilities
Grounding impedance, soil resistivity, step voltage, distribution potential, contact voltage and impedance angle in one instrument.
Four-wire, three-wire and two-wire test modes; grounding impedance uses the rated current method.
0.030 Ω – 2000 Ω impedance range with 0.001 Ω resolution in the lowest range.
Variable-frequency AC source with 45 Hz, 55 Hz and automatic dual-frequency measurement.
Short-circuit current output selectable at 1 A, 2 A, 3 A, 4 A and 5 A.
Maximum open-circuit voltage AC 400 V ±10 % and maximum short-circuit current AC 5 A ±10 % sine.
7-inch touch colour screen with measurement progress and prompt animation; 100-group storage and built-in thermal printer.
Soil resistivity electrode spacing settable from 1 m to 100 m; step voltage, distribution potential and contact voltage calculated as U = Z × Is.
Measurement Ranges and Accuracy
FunctionRangeAccuracy / FormulaResolution
Grounding impedance0.030 Ω – 1.999 Ω±0.5 % FS ±5 dgt0.001 Ω
Grounding impedance2.00 Ω – 19.99 Ω±0.5 % FS ±5 dgt0.01 Ω
Grounding impedance20.0 Ω – 199.9 Ω±0.5 % FS ±5 dgt0.1 Ω
Grounding impedance200 Ω – 2000 Ω±0.5 % FS ±5 dgt1 Ω
Soil resistivity0.000 Ωm – 9.999 Ωmρ = 2πaRX0.001 Ωm
Soil resistivity10.00 Ωm – 99.99 Ωmρ = 2πaRX0.01 Ωm
Soil resistivity100.0 Ωm – 999.9 Ωmρ = 2πaRX0.1 Ωm
Soil resistivity1000 Ωm – 9999 Ωmρ = 2πaRX1 Ωm
Soil resistivity10.0 kΩm – 99.9 kΩmρ = 2πaRX0.1 kΩm
Soil resistivity100 kΩm – 999 kΩmρ = 2πaRX1 kΩm
Step voltage / distribution potential / contact voltage0.000 kV – 1.999 kVU = Z × Is0.001 kV
Step voltage / distribution potential / contact voltage2.00 kV – 19.99 kVU = Z × Is0.01 kV
Step voltage / distribution potential / contact voltage20.0 kV – 199.9 kVU = Z × Is0.1 kV
Impedance angle0 – 359.9°—0.1°
Radian0 – 6.283—0.001
Technical Specifications
ParameterSpecification
FunctionGrounding impedance, soil resistivity, step voltage, distribution potential, contact voltage
Rated measurement power2000 W
Anti-interference50 Hz voltage 50 V
Reference conditions23 °C ±5 °C, below 70 % RH; auxiliary ground resistance 20 Ω ±10 %; voltage to ground < 10 V
Power supplyAC 220 V 10 A, 50 Hz
BacklightAdjustable brightness
Measurement modeFour-wire, three-wire and two-wire test
Measurement methodGrounding impedance: rated current method
Short-circuit current output1 A, 2 A, 3 A, 4 A, 5 A (5 settings)
Soil resistivity electrode spacingSettable 1 m – 100 m
Test frequency45 Hz, 55 Hz or automatic dual-frequency
Maximum short-circuit currentAC 5 A ±10 %, sine wave
Maximum open-circuit voltageAC 400 V ±10 %, sine wave
Display7-inch touch colour screen
Touch screenYes
Measurement indicationMeasurement progress display and measurement prompt animation
Dimensions540 mm × 440 mm × 210 mm
Standard test lineRed 15 m, black 15 m, yellow 10 m, green 10 m, yellow 1.5 m, green 1.5 m; one each
Auxiliary ground rods800 mm × 2; 200 mm × 2
Measurement timeGrounding impedance: about 1 minute per test
PrinterBuilt-in thermal printer
Print paper57 mm × 40 mm
Data storage100 groups; "Saved" indication; "Save failed, memory full" when full
Data reviewYes
Overflow displayOL symbol
Automatic shut-downNone
Power consumptionStandby: < 110 W; measurement: 2000 W
WeightInstrument: 27 kg; test line, auxiliary ground rods and bag: 5.5 kg
Working temperature and humidity-10 °C – 40 °C; below 80 % RH
Storage temperature and humidity-20 °C – 60 °C; below 70 % RH
Insulation resistance≥ 10 MΩ at 500 V between circuit and case
Withstand voltageAC 3700 V/rms between circuit and case
Electromagnetic characteristicsIEC61010-4-3; radio-frequency electromagnetic field ≤ 1 V/m
SafetyIEC61010-1; IEC1010-2-31; IEC61557-1, 5; IEC60529 (IP54); pollution degree 2; CAT III 300 V
Frequently Asked Questions
Q1.What measurements does the XHEP701A provide?
It measures grounding impedance, soil resistivity, step voltage, distribution potential, contact voltage and impedance angle. Grounding impedance supports two-wire, three-wire and four-wire test modes.
Q2.What is the grounding impedance range and accuracy?
The range is 0.030 Ω – 2000 Ω in four ranges, with accuracy ±0.5 % FS ±5 dgt. Resolution is 0.001 Ω in the lowest range, 0.01 Ω, 0.1 Ω and 1 Ω in the higher ranges.
Q3.What output current and test frequency does it use?
Short-circuit current output is selectable at 1 A, 2 A, 3 A, 4 A and 5 A. Test frequency is 45 Hz, 55 Hz or automatic dual-frequency; maximum short-circuit current is AC 5 A ±10 % sine and maximum open-circuit voltage is AC 400 V ±10 % sine.
Q4.How much data can it store and can it print?
It stores 100 groups and shows a saved indication; when memory is full it displays the save-failed message. A built-in thermal printer uses 57 mm × 40 mm paper.
Q5.What power and site conditions does it need?
It runs on AC 220 V 10 A, 50 Hz. The instrument weighs 27 kg and measures 540 mm × 440 mm × 210 mm; working conditions are -10 °C to 40 °C at below 80 % RH.