The XHDJ706 is a digital earth resistance and soil resistivity tester for power-system grounding checks. It covers ground resistance from 0.00 Ω to 30.00 kΩ, soil resistivity from 0.00 Ωm to 9999 kΩm, and ground voltage from 0.00 V to 600 V AC.
For tower and distribution grounding, the four-wire connection separates the voltage and current circuits and removes the effect of contact resistance and test-lead resistance. The meter also checks the connection status of each interface and the interference voltage and frequency of the ground network before the reading is taken.
For power transmission and distribution field crews who test grounding at towers, substations and distribution equipment.
| Range | Accuracy | Resolution | |
|---|---|---|---|
| Ground resistance (R) | 0.00 Ω – 30.00 Ω | ±2 % rdg ± 5 dgt | 0.01 Ω |
| Ground resistance (R) | 30.0 Ω – 300.0 Ω | ±2 % rdg ± 3 dgt | 0.1 Ω |
| Ground resistance (R) | 300 Ω – 3000 Ω | ±2 % rdg ± 3 dgt | 1 Ω |
| Ground resistance (R) | 3.00 kΩ – 30.00 kΩ | ±2 % rdg ± 3 dgt | 10 Ω |
| Soil resistivity (ρ) | 0.00 Ωm – 99.99 Ωm | ρ = 2πaR | 0.01 Ωm |
| Soil resistivity (ρ) | 100.0 Ωm – 999.9 Ωm | ρ = 2πaR | 0.1 Ωm |
| Soil resistivity (ρ) | 1000 Ωm – 9999 Ωm | ρ = 2πaR | 1 Ωm |
| Soil resistivity (ρ) | 10.00 kΩm – 99.99 kΩm | ρ = 2πaR | 10 Ωm |
| Soil resistivity (ρ) | 100.0 kΩm – 999.9 kΩm | ρ = 2πaR | 100 Ωm |
| Soil resistivity (ρ) | 1000 kΩm – 9999 kΩm | ρ = 2πaR | 1 kΩm |
| Ground voltage | AC 0.00 V – 600 V | ±2 % rdg ± 3 dgt | 0.01 V |
| Parameter | Specification |
|---|---|
| Function | Two-wire, three-wire and four-wire ground resistance; soil resistivity; ground voltage |
| Ground resistance range | 0.00 Ω – 30.00 kΩ, automatic range shift |
| Soil resistivity range | 0.00 Ωm – 9999 kΩm, automatic range shift |
| Ground voltage range | AC 0.00 V – 600 V |
| Measurement method | Ground resistance: rated current change-pole method; soil resistivity: four-pole Wenner method; ground voltage: average rectification |
| Test frequency | 128 Hz |
| Short-circuit test current | AC > 20 mA, sine wave |
| Open-circuit test voltage | AC 28 V max |
| Electrode spacing | 1 m – 100 m, settable |
| Display | 4-digit large LCD, 111 mm × 68 mm; display field 108 mm × 65 mm; off-white backlight |
| Data storage | 500 groups; MEM storage indication; FULL symbol when full |
| Power supply | 6 × 1.5 V LR14 alkaline batteries (9 V); continuous standby > 100 hours |
| Automatic shut-down | APO indication; auto power-off after 15 minutes |
| Dimensions | 240 mm (L) × 188 mm (W) × 85 mm (H) |
| Weight | Instrument 1280 g including battery; test line 1300 g; auxiliary ground rods 720 g (4 pieces) |
| Operating conditions | -10 °C – 40 °C; < 80 % RH |
| Storage conditions | -20 °C – 60 °C; < 70 % RH |
| Overload protection | Ground resistance: AC 280 V / 3 s between H-E and S-ES ports |
| Insulation resistance | ≥ 20 MΩ at 500 V between circuit and case |
| Withstand voltage | AC 3700 V/rms between circuit and case |
| Standards | IEC61010-1 (CAT III 300 V, CAT IV 150 V, pollution degree 2); IEC61010-031; IEC61557-1; IEC61557-5; JJG 366-2004; IEC61326 (EMC) |