Portable outdoor ready unit with four wheels, IP43
Very easy to use "turn&click" single
rotary knob interface
Surge/Thump energy 2,048
Joule DC testing/surging/thumping up to 32 kV, burning up to 32 kV Working power 2000VA Prelocation methods: ARC Multishot, ICE and DECAY, low voltage pulse Built-in safety circuits for earth connection monitoring (F-Ohm) and touch potential monitoring (F-Voltage)
Feature
• 10.1-inch full-color TFT touch screen;
• Embedded system, safe, stable, simple display and operation mode;
• With the function of testing cable wave velocity, cable length and fault distance;
• Fully automatic continuous sampling, waveform capture at all times, timely and accurate.
• With automatic test range setting, automatic waveform analysis and display of test distance.
• Full Chinese menu, touch and coding button two operation modes, simple, fast and reliable.
• With low-voltage pulse method, high-voltage flashover method, multiple pulse method (8 times) test technology, waveform display is smooth and easy to read.
• When using the multiple pulse method, it is used with a pulse coupler to display 8 groups of high and low voltage waveform comparisons, which is convenient for automatic test distance, manual analysis and distance measurement.
• The instrument has powerful data processing capabilities, which is convenient for users to manage and archive waveform files.
• It has a massive test waveform storage function: the waveforms tested on site can be conveniently stored in the instrument in the order specified by the Chinese naming regulations, so that they can be called up for observation and analysis at any time; it can store more than 8,000 low-voltage pulse and high-voltage flashover waveform records, and more than 250 multiple pulse waveform records. The waveform files can be imported into the computer software for management and analysis using USB communication.
• Ultra-high brightness, LED backlight brightness up to 280nit, resolution 1024*600, easy to operate in direct sunlight.
• Built-in large-capacity lithium battery pack, supports fast charging, and can be tested in an environment without power supply.
Technical Parameters
General features | |
Portable cable fault location system | |
Graphical interface | Graphical interface, more intuitive and easy to operate. |
Operation | Turn and click a single knob (jog dial) on the control unit |
Data management | General database |
Data Synchronization | Universal Serial Bus |
Control unit | |
Display | Industrial grade TFT color panel with LED backlight |
Anti-glare | have |
Multi-touch | have |
LCD size | 10" |
Aspect Ratio | 16:9 |
Resolution | 1024 x 768 Full HD |
Brightness | 450 cd/m² |
Safety | |
Adaptability | CE Compliance;EN 61010,EN 50191,VDE 0104,VDE 015,DGUV 203-034(BGI 891) |
Discharge and grounding devices | 72kJ, equivalent to the energy stored in a 10µF capacitor charged to 120kV DC fast charge: discharge time constant < 1 second |
System Status | Real-time monitoring and indication |
Intrinsically safe | Ground immediately when there is a power outage |
F-U safety interlock | Operating voltage connection monitoring (high voltage circuit) |
F-Ohm Safety Interlock | Operational earth connection monitoring (high voltage circuit) |
Security Features | Front panel: power on/off, lockout button switch, emergency stop, residual pressure indicator light, high voltage switch; Control unit: Knob (jog dial) |
Safety devices | System grounding status indicator, power input protection device, high voltage room monitoring through door contact, external safety device |
Power input monitoring | Overvoltage protection, undervoltage protection, residual current device (RCD) |
Defining Wiring | There is a switchboard inside the system |
System function
1.Use DC or high-voltage pulse to make the cable fault point flash over and discharge
2.Use the traveling wave reflection principle to make a rough measurement of all types of cable main insulation faults
3. Use the acoustic and magnetic synchronization method to make a precise measurement of all types of cable main insulation faults
I,High voltage surge generator
Output mode | DC, Single, Cycle |
Output voltage | 0-8kV,0-16kV,0-32kV |
Built-in capacitor | 64uF,16uF,4uF |
Discharge energy | 2048J @ each voltage level |
Impact power | 2000VA |
Impulse rate | Automatic impact for about 6 seconds, manual impact for any control time |
Surge voltage levels switch | Manual |
Voltage adjustment type | Continuous |
Indication | High-voltage side voltage metering, indication of output voltage and current in real time |
Operating modes switch | Manual |
Coupler | Built-in multiple pulse sampling box |
Safe protection | With zero start protection function, safe and reliable |
Discharge | Unique high-voltage measurement design, in the stop state, it will automatically discharge the internal capacitance of the device |
Working power | AC 220V±15% ,50Hz±2Hz(60Hz) |
DC withstand voltage testing | Output voltage adjustable and indication range 0-32kV, output current indication range 0-20A |
Burn current | Fault conditioning (burning) with current up to 60 mA @ 32 kV, 120 mA @ 16kV, 240mA@8kV |
Safety | Over-voltage, Over-current, Overheating protection. Automatic discharge after operation |
Protection rating | Not lower than IP54 |
Dimensions(mm) | 534L×444W×805H mm |
Total weight | Not more than 130kg |
II,TDR cable fault locatorII,TDR cable fault locator | |
Test method | Low voltage pulse, Impulse current, Impulse voltage, ARC multipls pulse |
Sampling rate | 1MHz~400MHz |
Pulse output | Unipolar |
Pulse Amplitude | 300V |
Pulse width | 0.15μS/0.30μS /0.60μS/1.20μS/2.4μS/5.0μS/7.5μS/10μS |
Measurement scope | ≥120km |
Measurement range | 100m/300m/500m/1km/3km/5km/10km/25km/50km/100km |
Minimum resolution | 0.07m |
Measurement error | ≤±(0.5%×L+1m),L is cable length |
Signal gain | 0…100%,adjustable |
Propagation speed | 10…999.9m/µs |
Output Impedance | Automatic match |
Trigger | Automatic continute |
Result analysis | Automatic measure fault distance |
Working conditions | temperature -25ºC~+65ºC, relative humidity 85%, atmospheric pressure 750±30mmHg |
III.Acoustic and magnetic synchronous cable fault pinpointer | |
Location mode | Standard mode, enhanced mode, noise reduction mode, custom mode (ms, waveform) |
Location method | Intelligent time difference method, step voltage method, electromagnetic inspection method, acoustic measurement method |
Positioning accuracy | Fixed point: 0.1m, Path: 0.1m, Step voltage: 0.1m |
Display | TFT ultra-bright 5-inch, 800×480 true color |
Language | Graphical language is more intuitive |
Gain | 120dB, fully automatic adjustment, also can be adjusted manually |
Frequency range | 100~1600Hz |
Dynamic Range | 0~112dB(16 gears) |
Synchronous trigger | Acoustic fully automatic synchronous trigger; magnetic field fully automatic synchronous trigger |
Detection range | 0.00~99.99ms,75mV~75V |
Probe | Automatic mute, fully digital metal intelligent probe |
Headphone | 350Ω strong noise reduction and anti-interference technology |
Working power | 4*18650 Standard lithium battery |
Working hours | More than 8 hours |
Ambient temperature | -25~65ºC;Relative humidity:≤90% |
Weight | Host 0.6kg;Sensor 1.4kg |
Waterproof grade | IP65 |
V Test cables
(Note: Due to the existence of 35kV high voltage, special high voltage cables are made and should be kept away from the site during operation.) | |
High voltage output cable | core wire 2.5mm2 red, withstand voltage 50kV DC, with shielding layer, outer diameter 14mm, length can be customized according to customer's requirements, including installation of large spool. Standard length of HV output cable is 5m. |
Ground cable | grounding 3-column - main core 16mm2 transparent color, branch 2.5mm2, length can be customized according to customer's requirements, including installation of small spool.Standard length of ground cable is 5m. |
Prelocating methods ARC Multishot: The Arc Reflection Method overlays and compares a low voltage reference trace and a high voltage fault trace captured via capacitor discharge through an inductive (coil-type) filter.
8 comparative measurements per ARM shot are displayed (Multishot feature), and the results are evaluated automatically. ICE/Surge Pulse: After fault ignition via capacitor discharge, the Impulse Current or Surge Pulse method measures the current component of the travelling wave, This technique is suitable for long cables and PILC cables.
DECAY: After fault ignition via HV DC source, the DECAY method measures the voltage component of the travelling wave. This technique is suitable for very long cables, HV transmission cables and faults with very high breakdown voltage.
IFL: Intermittent Fault Locating; to find intermittent faults with temporarily changing characteristics like they often occur in street lighting systems.
V Test cables
V Test cables
I,Highsurge generator
I,High voltage surge generator
System function
System fu