The XHDJ706 measures ground resistance, soil resistivity and ground voltage in one instrument. Its ground resistance range is 0.01 Ω to 30.00 kΩ, soil resistivity range is 0.00 Ωm to 9999 kΩm, and ground voltage range is AC 0.00 V to 600 V.
The meter supports precision four-wire, three-wire and simple two-wire ground resistance tests. Soil resistivity uses the four-pole Wenner method with an electrode spacing of 1 m to 100 m, calculated as ρ = 2πaR. A four-digit LCD with backlight shows the reading, and 500 groups can be stored for later review.
For telecom, computer-room, oil field and gas station teams that maintain grounding and lightning protection systems.
| Range | Accuracy | Resolution | |
|---|---|---|---|
| Ground resistance (R) | 0.00 Ω – 30.00 Ω | ±2 % rdg ± 5 dgt | 0.01 Ω |
| Ground resistance (R) | 30.0 Ω – 300.0 Ω | ±2 % rdg ± 3 dgt | 0.1 Ω |
| Ground resistance (R) | 300 Ω – 3000 Ω | ±2 % rdg ± 3 dgt | 1 Ω |
| Ground resistance (R) | 3.00 kΩ – 30.00 kΩ | ±2 % rdg ± 3 dgt | 10 Ω |
| Soil resistivity (ρ) | 0.00 Ωm – 99.99 Ωm | ρ = 2πaR | 0.01 Ωm |
| Soil resistivity (ρ) | 100.0 Ωm – 999.9 Ωm | ρ = 2πaR | 0.1 Ωm |
| Soil resistivity (ρ) | 1000 Ωm – 9999 Ωm | ρ = 2πaR | 1 Ωm |
| Soil resistivity (ρ) | 10.00 kΩm – 99.99 kΩm | ρ = 2πaR | 10 Ωm |
| Soil resistivity (ρ) | 100.0 kΩm – 999.9 kΩm | ρ = 2πaR | 100 Ωm |
| Soil resistivity (ρ) | 1000 kΩm – 9999 kΩm | ρ = 2πaR | 1 kΩm |
| Ground voltage | AC 0.00 V – 600 V | ±2 % rdg ± 3 dgt | 0.01 V |
| Parameter | Specification |
|---|---|
| Function | Two-wire, three-wire and four-wire ground resistance; soil resistivity; ground voltage |
| Ground resistance range | 0.00 Ω – 30.00 kΩ, automatic range shift |
| Soil resistivity range | 0.00 Ωm – 9999 kΩm, automatic range shift |
| Ground voltage range | AC 0.00 V – 600 V |
| Measurement method | Ground resistance: rated current change-pole method; soil resistivity: four-pole Wenner method; ground voltage: average rectification |
| Test frequency | 128 Hz |
| Short-circuit test current | AC > 20 mA, sine wave |
| Open-circuit test voltage | AC 28 V max |
| Electrode spacing | 1 m – 100 m, settable |
| Display | 4-digit large LCD, 111 mm × 68 mm; display field 108 mm × 65 mm; off-white backlight |
| Data storage | 500 groups; MEM storage indication; FULL symbol when full |
| Power supply | 6 × 1.5 V LR14 alkaline batteries (9 V); continuous standby > 100 hours |
| Automatic shut-down | APO indication; auto power-off after 15 minutes |
| Dimensions | 240 mm (L) × 188 mm (W) × 85 mm (H) |
| Weight | Instrument 1280 g including battery; test line 1300 g; auxiliary ground rods 720 g (4 pieces) |
| Operating conditions | -10 °C – 40 °C; < 80 % RH |
| Storage conditions | -20 °C – 60 °C; < 70 % RH |
| Overload protection | Ground resistance: AC 280 V / 3 s between H-E and S-ES ports |
| Insulation resistance | ≥ 20 MΩ at 500 V between circuit and case |
| Withstand voltage | AC 3700 V/rms between circuit and case |
| Standards | IEC61010-1 (CAT III 300 V, CAT IV 150 V, pollution degree 2); IEC61010-031; IEC61557-1; IEC61557-5; JJG 366-2004; IEC61326 (EMC) |