Advanced cable fault diagnosis solution featuring portable design and precision high-voltage components.
The XHHV512-12L low voltage pulse generator is a portable integrated device designed for shock discharge during low-voltage cable fault testing. Featuring high-precision components and advanced high-frequency high-voltage technology, this unit offers exceptional operational efficiency in a compact, user-friendly package.
| 1. Safety Ground | Essential for instrument shell grounding to prevent electrical hazards |
| 2. High-voltage Ground | Critical connection point to prevent voltage leakage and component damage |
| 4. Discharge Button | Manual discharge activation (max 1s press duration) |
| 5. High Voltage Start | Initiates high voltage output when indicator light is active |
| 8. Voltage Adjustment | Precision knob for output voltage regulation |
| 13-14. Meters | Real-time display of high voltage side current and output voltage |
| Parameter | Value |
|---|---|
| Impact High Voltage | 0~12kV |
| Built-in Capacitor | 12μF |
| Output Voltage Polarity | Negative |
| Impact Power | 250W@peak |
| Working Modes | Adjustable impulse rate or single shot |
| Cable Lengths | 2m output line, 3m ground line, 1.8m power line |
| Protections | 65°C over-temperature, 8mA over-current (3s threshold) |
| Dimensions | 540L * 300W * 450H (mm) |
| Power Supply | AC220V±15%, 50Hz±2Hz (60Hz available) |
| Operating Temperature | -20~+60°C |