A DC high voltage test set for arresters, cables, transformers, breakers and generators, available in four output configurations from 60 kV / 2 mA to 120 kV / 2 mA.
The set applies a DC voltage to the specimen and measures the leakage current that flows at that voltage. On a zinc oxide arrester the current at a defined voltage is the value that matters; on a cable or a transformer it is the trend across tests that shows whether the insulation is drying out, tracking or degrading. Both readings come from the same run.
Voltage and current are sampled on the high voltage side, so the display shows what is present at the test object rather than a value reconstructed from the low voltage side. The 0.75UDC-1mA button sets the reference point used for arrester testing in one touch, with the precision stated for this platform.
The 120/2S document lists four configurations: 60 kV / 2 mA, 60 kV / 3 mA, 120 kV / 2 mA and 60 kV / 5 mA. Each is a separate build, and the control box weight differs between them (11.6 kg and 13 kg), so the configuration is fixed when the set is ordered. The table below is the reference for selection.
Typical use is preventive testing: arrester leakage at the reference voltage, DC withstand on cable after jointing, and insulation checks on transformers and breakers during a planned outage. The set is portable enough to be carried to the equipment instead of bringing the equipment to a laboratory.
| Configuration | Output voltage | Output current | Output power | Charging current | Control box | Multiplier |
|---|---|---|---|---|---|---|
| 60 kV / 2 mA | 60 | 2 | 120 | 3 | 11.6 | 2.3 |
| 60 kV / 3 mA | 60 | 3 | 180 | 4.5 | 11.6 | 2.3 |
| 120 kV / 2 mA | 120 | 2 | 240 | 3 | 13 | 3.2 |
| 60 kV / 5 mA | 60 | 5 | 300 | 7.5 | 11.6 | 2.3 |
| Parameter | Value |
|---|---|
| Voltage measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Current measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Ripple factor | <= 0.5 % |
| 0.75UDC-1mA button | Precision <= 1.0 % |
| Working mode | 30 min at rated load; 10 min at 1.1 times rated voltage |
| Working environment | -10 C to +40 C, <= 85 % RH, altitude below 1500 m |
Yes. The 0.75UDC-1mA function is provided for zinc oxide arrester testing, and the same DC output is used for cable, transformer, breaker and generator insulation tests within the configuration rating.
The voltage decides the insulation class you can test and the current decides how much capacitive load you can charge in reasonable time. Send the highest test voltage and the largest capacitance in your list and we will match the configuration.
DC only. The set is a DC high voltage generator; it does not provide an AC or power-frequency output.
Send the highest test voltage, the largest specimen capacitance and whether arrester leakage testing is required, and we will confirm the configuration and the accessory set.