A 10 kVA oil-type hipot tester with a 100 kV AC output for transformer windings, bushings and substation equipment, built for planned maintenance and factory insulation tests.
A transformer is tested at power frequency to prove the insulation of windings, bushings and tap leads. The 100 kV AC output covers the insulation levels of distribution and sub-transmission transformers, and the 10 kVA rating matches the charging current of the winding capacitance within the 30-minute duty.
The high-voltage winding and core are immersed in transformer oil. The oil provides the dielectric strength needed for a 100 kV winding and carries heat from the coils to the tank wall. The tank is sealed and the portable frame allows the set to be moved between test positions.
The overcurrent relay is set from the expected specimen current and the current rate switch. The time relay is set for the specified hold time. The regulator starts at zero, the voltage is raised evenly to the test level, the timer is started, and the regulator is returned to zero before the supply is switched off.
The manual specifies an ambient temperature of 0 to 40 C, an altitude below 1000 m and a relative humidity below 85 %. The workplace should be free of explosive or corrosive gases, steam and chemical dust that could affect insulation.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| AC | 100 kV | 100 mA | 10 kVA | 200/380 V, 50/26 A | 1000 | 10 C / 30 min |
Yes. The 100 kV AC output is applied to the winding with the other winding earthed, and the insulation is proved at the specified test voltage for the specified time.
The rated duty limits the winding temperature rise to 10 C. Longer sequences should be arranged with cooling time between specimens.
The set is supplied with a matching control box containing the autotransformer, overcurrent relay and time relay. The transformer and control box are separate pieces.
Send the transformer ratings, winding voltages and required test voltage, and we will confirm that the XHYB-10/100 covers the outage list.