A 10 kVA oil-immersed AC/DC hipot tester for industrial power systems, with 100 kV AC and 140 kV DC outputs for switchgear, motors, busbars and insulation materials.
Switchgear insulation, busbar supports and current transformer barriers are tested at power frequency before a cubicle is returned to service. The 100 kV AC output covers the insulation levels of the cubicles used in 66 kV and 110 kV systems, and the 10 kVA rating is sufficient for the capacitance of a single bay.
Motor and generator windings are tested at DC to measure insulation resistance and leakage current without the charging current of an AC test. The 140 kV DC output covers machines and cable sections in the same voltage class, and the microammeter gives a direct leakage reading at each voltage step.
Boards, bushings, insulating boots and other materials are tested between the high-voltage electrode and earth. The test voltage is raised to the specified level and held, and the leakage current is recorded. The 30-minute duty and 10 C temperature rise keep the transformer within its thermal limit during a sequence of samples.
The specimen is earthed and discharged before connections are changed. In DC mode the filter capacitor is also discharged, and the discharge rod is used on the specimen before it is touched. The earth terminal of the control box, the transformer tank and the specimen earth are bonded to the station earth.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| DC | 140 kV | 100 mA | - | 380 V, 50/26 A | 1000 | 10 C / 30 min |
Yes. The 100 kV AC output is used for switchgear, busbar and bushing insulation within that class, with the test voltage set by the applicable standard.
For DC withstand and leakage tests on motors, generators, cables and arresters where a DC test is specified. The DC output is obtained from the same transformer through a rectifier and filter.
The manual lists test lines, a power cord, the hipot tester, the control box, a high-voltage wire and a ground wire. A discharge rod is used for safety after the test.
Send the equipment list and the AC and DC test voltages for each item, and we will confirm whether the XHYB-10/100 covers the schedule.