A black oil-immersed AC/DC hipot tester with 100 kV AC and 140 kV DC outputs, 10 kVA rating and a control box with overcurrent trip for breakdown and withstand testing.
The set raises the voltage on the specimen until the specified test level is reached and holds it for the required time. If the insulation breaks down, the current rises sharply and the overcurrent relay trips the primary circuit. The same relay protects the transformer during a flashover, and the regulator is returned to zero before the specimen is handled.
The 100 kV AC output is used for cable, bushings and switchgear in the 66 kV and 110 kV classes. The voltage is raised with the autotransformer and read on the panel voltmeter. The 10 kVA rating and 30-minute duty cover a single bay or a cable section within the thermal limit.
In DC mode the output is rectified and filtered, reaching 140 kV at 100 mA. The microammeter shows the leakage current at the test voltage, and a rising current at a steady voltage indicates insulation distress. The DC test avoids the charging current that flows during an AC test on a long cable.
The transformer is oil immersed, with the core and windings inside a sealed tank. The oil provides insulation and cooling, and the winding temperature rise is limited to 10 C at rated output. After the test the specimen and the filter capacitor are discharged, and the discharge rod is applied before leads are changed.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| AC | 100 kV | 100 mA | 10 kVA | 200/380 V, 50/26 A | 1000 | 10 C / 30 min |
| DC | 140 kV | 100 mA | - | 380 V, 50/26 A | 1000 | 10 C / 30 min |
The overcurrent relay trips the primary circuit when the specimen current exceeds the set value, which is how a breakdown is caught. The trip level is set from the expected specimen current.
The transformer and control box are mounted on a black portable frame. The housing color does not affect the electrical rating; the oil tank and windings are the same 10 kVA construction.
The 100 kV AC output covers 66 kV and 110 kV cable, bushings and switchgear. The 140 kV DC output is used for leakage and DC withstand tests on the same classes.
Send the specimen type, voltage class and breakdown current setting, and we will confirm the XHYB series set and the test sequence.