An electronic-control AC/DC hipot tester built on a 10 kVA oil-immersed transformer, with 100 kV AC and 140 kV DC outputs for transformers, cable and substation equipment.
The control box carries the autotransformer, the voltmeter, the overcurrent relay and the time relay. The operator sets the current trip and the hold time on the panel, raises the voltage with the regulator and reads the applied voltage from the meter. The electronic relays trip the primary circuit on overcurrent, so a breakdown does not depend on the operator reacting to a flash.
The 100 kV AC output is used for power transformer windings, bushings and tap leads in the 66 kV and 110 kV classes. The 10 kVA rating matches the charging current of a transformer winding within the 30-minute duty, and the oil-filled tank keeps the winding temperature rise to 10 C at rated output.
For DC tests the secondary output passes through a high-voltage silicon stack and a filter capacitor. The DC amplitude reaches 140 kV, and the panel microammeter reads the leakage current through the specimen. A current that rises at a steady voltage is the signal to stop the test and inspect the insulation.
The transformer core is built from cold-rolled silicon steel, and the windings are arranged concentrically around it inside the oil tank. The oil insulates the high-voltage winding and transfers heat to the tank wall. The tank, the control box and the test leads are transported as separate pieces.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| AC | 100 kV | 100 mA | 10 kVA | 200/380 V, 50/26 A | 1000 | 10 C / 30 min |
| DC | 140 kV | 100 mA | - | 380 V, 50/26 A | 1000 | 10 C / 30 min |
The power stage is a hand-driven autotransformer, while the overcurrent and time functions use electronic relays. The panel meters show the applied voltage and, in DC mode, the leakage current.
The 100 kV AC output is intended for 66 kV and 110 kV transformer windings, bushings and switchgear, with the test voltage taken from the applicable standard.
The DC voltage is produced by rectifying and filtering the AC secondary. The DC amplitude is about 1.41 times the AC rms value, which is why a 100 kV AC winding gives a 140 kV DC output.
Send the transformer rating, winding voltage and required AC and DC test levels, and we will confirm the XHYB-10/100 configuration.