The XHDP series covers 30 kV, 50 kV, 60 kV and 80 kV peak ratings on a common platform: the same 4 kg controller drives any of the boosters, and only the booster changes with the voltage class. A workshop that tests 10 kV distribution cables today and 35 kV cable later can add a booster instead of replacing the whole set.
Every rating runs at three fixed frequencies - 0.1 Hz, 0.05 Hz and 0.02 Hz - with 1.1 µF, 2.2 µF and 5.5 µF load capability, so a specimen with a large capacitance is tested at the lower frequency rather than with a larger source. Measurement accuracy is 3 %, waveform distortion is within 5 % and protection acts within 10 ms.
The series exists for organisations that have to cover several voltage classes with a fleet that stays manageable in size and cost.
| Model | Rated voltage | 0.1 Hz | 0.05 Hz | 0.02 Hz | Supply fuse | Controller / booster |
|---|---|---|---|---|---|---|
| XHDP-30 | 30 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 10 A | 4 kg / 20 kg |
| XHDP-50 | 50 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 40 kg |
| XHDP-60 | 60 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 50 kg |
| XHDP-80 | 80 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 50 kg |
| Parameter | Value |
|---|---|
| Output frequencies | 0.1 Hz, 0.05 Hz and 0.02 Hz, selectable |
| Measurement accuracy | 3 % |
| Peak voltage error | ≤ 3 % |
| Waveform distortion | ≤ 5 % |
| Protection operating time | ≤ 10 ms |
| Supply | 220 V ± 5 %, 50 Hz ± 5 Hz; a portable generator needs more than 3 kW with a stable 220 V / 50 Hz output |
| Service conditions | Indoor or outdoor, -10 °C to +40 °C, humidity ≤ 85 % RH |