This XHDP configuration is specified around protection behaviour: over-voltage protection, over-current protection on both the high voltage and the low voltage side, and an operating time of 10 ms or less. On a 0.1 Hz test the specimen can break down at any point in a very slow cycle, and the speed of the trip is what decides whether the booster survives the event.
The same set offers 30, 50, 60 and 80 kV peak ratings at 0.1 Hz, 0.05 Hz and 0.02 Hz, with load capability of 1.1 µF, 2.2 µF and 5.5 µF. Closed-loop negative feedback on both sides keeps the output free of capacitance rise, so the voltage the operator sets is the voltage the specimen sees.
This set is chosen by teams whose procedures put protection response and record keeping ahead of portability.
| Model | Rated voltage | 0.1 Hz | 0.05 Hz | 0.02 Hz | Supply fuse | Controller / booster |
|---|---|---|---|---|---|---|
| XHDP-30 | 30 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 10 A | 4 kg / 20 kg |
| XHDP-50 | 50 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 40 kg |
| XHDP-60 | 60 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 50 kg |
| XHDP-80 | 80 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 50 kg |
| Parameter | Value |
|---|---|
| Output frequencies | 0.1 Hz, 0.05 Hz and 0.02 Hz, selectable |
| Measurement accuracy | 3 % |
| Peak voltage error | ≤ 3 % |
| Waveform distortion | ≤ 5 % |
| Protection operating time | ≤ 10 ms |
| Supply | 220 V ± 5 %, 50 Hz ± 5 Hz; a portable generator needs more than 3 kW with a stable 220 V / 50 Hz output |
| Service conditions | Indoor or outdoor, -10 °C to +40 °C, humidity ≤ 85 % RH |