logo
Home > Products >
AC DC Hipot Tester
>
0.1Hz VLF Hipot Tester 50kV Cable Insulation Test Principle and Source Size

0.1Hz VLF Hipot Tester 50kV Cable Insulation Test Principle and Source Size

Product Details:
Place of Origin: Xi'an, Shaanxi, China
Brand Name: XZH TEST
Certification: CE, ISO
Model Number: XHDP Series
Detail Information
Place of Origin:
Xi'an, Shaanxi, China
Brand Name:
XZH TEST
Certification:
CE, ISO
Model Number:
XHDP Series
Model NO.:
XHDP SERIES
Power:
Electricity
Customized:
Customized
Color:
Black
Language:
English
Protection Function:
Over-Voltage Protection, Over-Current Protection.
Typical Application:
Power Cables Below 35 Kv; Generators Hipot Test.
Power Supply:
AC50 Hz,220V ±5%
Transport Package:
Exported Wooden Case With Foam Inside
Trademark:
XZH TEST
Origin:
China
HS Code:
903033900
Supply Ability:
2000piecs/Year
Customization:
Available
After-sales Service:
24/7 Online Service
Warranty:
1 Year
Highlight:

High Light

Highlight:

50kV VLF AC hipot tester

,

0.1Hz cable withstand voltage tester

,

AC DC hipot tester with warranty

Trading Information
Minimum Order Quantity:
1 unit
Packaging Details:
Wooden case
Delivery Time:
5-8 work days
Payment Terms:
T/T
Supply Ability:
2000 units/month
Product Description
0.1 Hz VLF Test Method

0.1Hz VLF Hipot Tester 50kV Cable Insulation Test Principle and Source Size

Why a 0.1 Hz test can replace a power-frequency test on cable, what changes in the source, and what the method does not change about the stress on the insulation.

0.1 Hz output
50 kV peak model
1/500 of 50 Hz current
3 % accuracy

The problem with 50 Hz on a cable

A cable is a large capacitor. When AC voltage is applied, the current it draws is proportional to frequency, capacitance and voltage: raise any of the three and the source has to supply more. At 50 Hz a long XLPE feeder can demand a substantial capacitive current at test voltage, which is why power-frequency testing of cables is normally done with a large test transformer or a resonant set rather than with something that can be carried into a substation.

Xhdp Series 30/50/60/80kv Vlf Withstand Voltage Generator AC Sine Wave Hipot Tester

Why lowering the frequency shrinks the source

Reduce the frequency by a factor of 500 and the capacitive current falls by the same factor. At 0.1 Hz the source sees roughly one five-hundredth of the current it would have to supply at 50 Hz, and that single relationship is the whole basis of VLF testing: the applied voltage is unchanged, only the rate at which it is delivered. The practical consequence is that the equipment drops from a vehicle-mounted system to a controller and a booster that two people can carry to the cable.

What the method does not change

The test voltage and its duration are set by the standard applied on site, not by the instrument. VLF changes how that voltage is generated, not what the procedure requires: the acceptance criteria, the phase-by-phase sequence, the discharge and earthing steps all stay as written. The long cycle does change how the test feels in practice - at 0.1 Hz one full wave takes ten seconds, so a test of tens of minutes is a slow, deliberate process rather than a quick flash test, and the operator has time to watch the waveform and the leakage current as they develop.

Where the method does not apply

VLF withstand testing is intended for capacitive specimens - cables, motors, generators, bushings, capacitors. It is not suitable for resistive specimens such as zinc oxide surge arresters, whose behaviour under test depends on the waveform in a way the 0.1 Hz method does not reproduce. Knowing this boundary is as useful as knowing the method itself, because it prevents an instrument being specified for a job it was never designed to do.

How this applies to the XHDP series

Every XHDP set is built around this principle: three fixed frequencies (0.1 Hz, 0.05 Hz, 0.02 Hz) with load capability of 1.1 µF, 2.2 µF and 5.5 µF, so the frequency is chosen to fit the specimen instead of the specimen being refused. Ratings run from 30 kV to 80 kV peak, and the set is built to be carried to the cable rather than the cable brought to a laboratory.

Frequently asked questions

Is a 0.1 Hz test equivalent to a 50 Hz test?

The equivalence is based on the same peak voltage stress on the insulation over a longer cycle, and it is the basis on which VLF testing is accepted for cable insulation. The test voltage and duration must follow the standard or the utility procedure that applies to the cable being tested.

Why does the cable draw less current at 0.1 Hz?

The capacitive current of a cable is proportional to frequency, capacitance and voltage. Lowering the frequency from 50 Hz to 0.1 Hz reduces the current by a factor of about 500, which is why a portable controller and booster can do the job of a much larger source.

Can every specimen be tested at 0.1 Hz?

No. The method is intended for capacitive specimens such as cable, motors and generators. Resistive specimens such as zinc oxide arresters are outside its scope, and the applicable standard decides whether VLF is acceptable for a particular cable type.

How long does one test take?

The test time is set by the standard in use. The output frequency can be 0.1 Hz, 0.05 Hz or 0.02 Hz, and a lower frequency is selected when the specimen capacitance is too high for the 0.1 Hz load limit.

Method check

Tell us the cable type, voltage class and test standard you work to, and we will confirm whether a 0.1 Hz VLF set covers the procedure and which model to use.

Ratings & Review

Overall Rating

5.0
Based on 50 reviews for this supplier

Rating Snapshot

The following is the distribution of all ratings
5 stars
100%
4 stars
0%
3 stars
0%
2 stars
0%
1 stars
0%

All Reviews

N
Nikolaos Papadopoulos
Greece Jul 7.2026
Η συσκευή XHDP‑80M δοκιμής υπερβολικά χαμηλής συχνότητας έχει εξαιρετική απόδοση για την ομάδα διανομής μας. Πραγματοποιήσαμε δοκιμές αντοχής σε υπόγεια καλώδια 20kV στον υποσταθμό Κερατέας κοντά στην Αθήνα. Η λειτουργία με οθόνη αφής είναι εύκολη, η προστασία ενεργοποιείται γρήγορα και οι μετρήσεις παραμένουν ακριβείς ακόμα στη μεσογειακή ζέστη. Ανθεκτική κατασκευή για εργασίες πεδίου, μειώνει σημαντικά τον χρόνο προετοιμασίας των δοκιμών. Συνιστάται ανεπιφύλακτα για τα συνεργεία ηλεκτρικής ενέργειας στην Ελλάδα.