A 10 kVA oil-immersed AC/DC hipot tester with 100 kV AC and 140 kV DC outputs, built for high-voltage cable, transformer and substation equipment insulation tests.
The 100 kV AC output covers cable and equipment classes that sit above the 50 kV range, including 66 kV and 110 kV cable systems and the transformers and switchgear in the same substations. The DC output reaches 140 kV from the same transformer, so DC withstand and leakage tests do not require a second high-voltage source.
The windings are immersed in oil inside a steel tank. The oil insulates the high-voltage winding and transfers heat from the coils to the tank surface. This is what allows a 100 kV transformer to be built at 10 kVA in a transportable frame rather than as a fixed laboratory installation.
In AC mode the secondary feeds the specimen directly. In DC mode the output passes through a high-voltage silicon stack and a filter capacitor, and the DC amplitude is about 1.41 times the AC rms value. The control box, overcurrent relay and time relay are used in both modes, with the DC microammeter added for leakage readings.
The autotransformer is returned to zero before each start. The overcurrent relay is set from the specimen current and the current rate switch, and the time relay is set for the hold time. A flashover or breakdown trips the primary circuit, and the regulator is brought back to zero before the specimen is discharged.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| AC | 100 kV | 100 mA | 10 kVA | 200/380 V, 50/26 A | 1000 | 10 C / 30 min |
| DC | 140 kV | 100 mA | - | 380 V, 50/26 A | 1000 | 10 C / 30 min |
It is used for 66 kV and 110 kV cable classes, power transformers, bushings and switchgear insulation, with the test voltage taken from the applicable standard.
The 10/100 has twice the output voltage and a larger oil tank. The 5/50 is a 50 kV AC / 70 kV DC set for 10 kV and 35 kV work; the 10/100 is for the 100 kV class.
30 minutes at rated output, with a winding temperature rise of 10 C. The set is allowed to cool between long test sequences.
Send the cable or equipment class and the required AC and DC test voltages, and we will confirm the XHYB-10/100 configuration.