A custom DC hipot tester with manual voltage boost, built from 60 kV to 300 kV. It is chosen where the operator wants direct control of the boost rather than an automatic sequence.
Some test procedures call for the operator to raise the voltage step by step and watch the leakage current between steps. A manual boost keeps that decision with the person at the control unit. The over-voltage and over-current limits are still set electronically, so the manual mode does not remove protection.
The set uses AIPWM correction on the PWM stage, which reduces the non-linearity that plain PWM control leaves in the output. The result is a smoother adjustment across the range and a ripple factor within the figure stated for the platform. Voltage and current are shown together, so a change in leakage is visible while the boost is in progress.
Total test time T1 and segment time T2 can be timed independently, and the timer can also be started at any voltage or current. That is useful when a procedure specifies a hold time at more than one voltage level, or when the time to reach a leakage threshold is itself the recorded value.
The control box and the multiplier are separate units. The control box is carried by one person and the multiplier by another, which keeps the set usable on a cable tray or in a switchgear room where a cart cannot go.
| Configuration | Output voltage | Output current | Output power | Charging current | Control box | Multiplier |
|---|---|---|---|---|---|---|
| 60 kV / 2-3 mA | 60 | 2 / 3 | 120 / 180 | 3 / 4.5 | 11.6 | 2.3 |
| 120 kV / 2-3 mA | 120 | 2 / 3 | 240 / 360 | 3 / 4.5 | 13 | 3.6 |
| 60 kV / 5-10 mA | 60 | 5 / 10 | 300 / 600 | 7.5 | 16 | 5.8 |
| 120 kV / 5-10 mA | 120 | 5 / 10 | 600 / 1200 | 7.5 | 17.6 | 6.3 |
| Parameter | Value |
|---|---|
| Voltage measurement error | +/- 1 % (full scale) +/- 1 digit |
| Current measurement error | +/- 1 % (full scale) +/- 1 digit |
| Ripple factor | <= 0.5 % |
| 0.75UDC-1mA button | Precision <= 0.5 % |
| Working mode | 30 min at rated load; 10 min at 1.1 times rated voltage |
| Working environment | -10 C to +40 C, <= 85 % RH, altitude below 1500 m |
No. Over-voltage and over-current protection are still set and active. Manual boost only means the rate of rise is controlled by the operator.
Yes. The timer can be started at any voltage or current, in addition to the total T1 and segment T2 functions.
The voltage and power class are fixed at build. A different test list should be quoted as a separate configuration.
Send the voltage steps, hold times and the specimen capacitance in your procedure, and we will quote the configuration with manual boost.