This XHDP configuration is aimed at cable work: a 0.1 Hz very low frequency AC hipot that replaces the power frequency test on XLPE cable, where the insulation capacitance would otherwise call for a resonant set of several hundred kilograms. The three ratings offered - 30 kV, 50 kV and 80 kV peak - map onto 10 kV, 15 kV and 35 kV cable classes.
Choosing 0.1 Hz instead of 50 Hz cuts the capacity the source must supply to about one five-hundredth, so a 4 kg controller and a booster of 20 to 50 kg do the job. The set runs at 0.1 Hz, 0.05 Hz and 0.02 Hz with 1.1 µF, 2.2 µF and 5.5 µF load capability, which covers a single-phase cable length typical of distribution feeders.
This is the set for organisations whose test object is almost always a length of cable.
| Model | Rated voltage | 0.1 Hz | 0.05 Hz | 0.02 Hz | Supply fuse | Controller / booster |
|---|---|---|---|---|---|---|
| XHDP-30 | 30 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 10 A | 4 kg / 20 kg |
| XHDP-50 | 50 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 40 kg |
| XHDP-80 | 80 kV (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 15 A | 4 kg / 50 kg |
| Parameter | Value |
|---|---|
| Output frequencies | 0.1 Hz, 0.05 Hz and 0.02 Hz, selectable |
| Measurement accuracy | 3 % |
| Peak voltage error | ≤ 3 % |
| Waveform distortion | ≤ 5 % |
| Protection operating time | ≤ 10 ms |
| Supply | 220 V ± 5 %, 50 Hz ± 5 Hz; a portable generator needs more than 3 kW with a stable 220 V / 50 Hz output |
| Service conditions | Indoor or outdoor, -10 °C to +40 °C, humidity ≤ 85 % RH |
Overall Rating
Rating Snapshot
The following is the distribution of all ratingsAll Reviews