A VLF hi-pot set for shielded and forming cable, with high side sampling, built-in output protection and a printer that puts the test record on paper at the end of the run.
The XHDP series VLF hi-pot tester applies a 0.1 Hz AC withstand voltage to shielded cable and forming cable, where the capacitance of the insulation makes a 50 Hz test impractical. Boost, step-down, measurement and protection are controlled automatically, and the output waveform is shown on the display while the test runs. The integrated printer produces a record of the test at the end of the run.
On a shielded cable the insulation sits between the conductor and the metallic shield, so the test voltage is applied to the conductor and the shield is earthed. One phase is tested at a time; the capacitance to check against the load limit is that of a single phase to earth, not the whole three-phase circuit. The same arrangement applies to forming cable, where the insulation is tested before the cable goes into service.
| Model | Rated voltage / current | 0.1 Hz | 0.05 Hz | 0.02 Hz | Supply fuse | Controller / booster |
|---|---|---|---|---|---|---|
| XHDP-30 | 30 kV / 20 mA (peak) | ≤ 1.1 uF | ≤ 2.2 uF | ≤ 5.5 uF | 5 A | 4 kg / 25 kg |
| XHDP-50 | 50 kV / 30 mA (peak) | ≤ 1.1 uF | ≤ 2.2 uF | ≤ 5.5 uF | 15 A | 4 kg / 50 kg |
| XHDP-60 | 60 kV / 30 mA (peak) | ≤ 1.1 uF | ≤ 2.2 uF | ≤ 5.5 uF | 20 A | 4 kg / 55 kg |
| XHDP-80 | 80 kV / 30 mA (peak) | ≤ 1.1 uF | ≤ 2.2 uF | ≤ 5.5 uF | 20 A | 4 kg / 50 kg + 45 kg |
The controller uses a large display to show the output waveform, stores each test automatically and prints a report through the integrated printer. The interface can be switched between Chinese and English, and the set runs from 220 V +/- 5 %, 50 Hz, or from a portable generator with a stable output above 3 kW.
The test voltage is applied to the conductor and the metallic shield is earthed. One phase is tested at a time, so the capacitance to check against the load limit is the single-phase capacitance to earth.
Yes. The XHDP series is used for forming cable as well as for shielded cable, with the same 0.1 Hz withstand method and the same 30-80 kV range.
Over-voltage and over-current protection act in less than 20 ms. The high voltage output also has a built-in protective resistor, so no external resistor is needed.
Yes. Each test is stored automatically and printed through the integrated printer, so the voltage, current and outcome are on paper without manual transcription.
Send the cable type, the voltage class and the capacitance per phase, and we will confirm the rating and whether one booster covers the whole list.