An oil-immersed step-up test transformer rated 10 kVA, delivering 50 kV AC at 200 mA and 70 kV DC at 100 mA for insulation withstand tests on cable, transformers, motors and switchgear.
The unit is an oil-immersed test transformer with a tapped primary and a high-voltage secondary. In AC mode the secondary feeds the specimen directly at power frequency. In DC mode the same secondary output passes through a high-voltage silicon stack and a filter capacitor, producing a DC voltage whose amplitude is about 1.41 times the AC rms value. The change is made at the high-voltage side, so the control sequence stays the same.
The core is built from cold-rolled silicon steel laminations and the windings are arranged in a concentric pagoda shape, with the low-voltage winding inside and the high-voltage winding outside. The assembly sits in an oil-filled tank that provides insulation and carries heat away from the windings. The outer shell is a portable type, so the set can be moved between test bays without a fixed installation.
The matching control box contains an autotransformer, a voltmeter, an overcurrent relay and a time relay. The regulator is returned to zero before the start button is pressed; the voltage is then raised slowly to the specified value, the timer is started, and the regulator is brought back to zero before the supply is cut. If a flashover or breakdown occurs, the overcurrent relay trips the primary circuit.
The AC rating covers cable and equipment in the 10 kV and 35 kV classes, together with distribution transformers, motors and insulating materials. The DC rating is used for leakage current measurement on the same specimens and for arresters, where the manual calls for an added capacitor in the test circuit.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| AC | 50 kV | 200 mA | 10 kVA | 220/380 V, 50/26 A | 500 | 10 C / 30 min |
| DC | 70 kV | 100 mA | - | 380 V, 50/26 A | 500 | 10 C / 30 min |
AC output is 50 kV at 200 mA. DC output is 70 kV at 100 mA, obtained by rectifying and filtering the AC output, so the DC amplitude is higher than the AC rms value.
The oil provides dielectric insulation between windings and carries heat from the core and coils. It is also why the set can be built compactly for a 10 kVA rating.
Yes. The 50 kV AC output covers 10 kV and 35 kV cable classes, with the exact test voltage taken from the standard applied on site.
Send the highest test voltage, the specimen type and the required AC or DC output, and we will confirm the XHYB-5/50 configuration and accessories.