A 70 kV DC, 100 mA oil-immersed test set for leakage current measurement, with the microammeter reading the current that flows through the specimen at the applied voltage.
The AC secondary voltage is rectified by a high-voltage silicon stack and smoothed by a filter capacitor. The resulting DC amplitude is about 1.41 times the AC rms value, which is why a 50 kV AC winding produces a 70 kV DC output. The capacitor is connected to earth at one end, and the specimen is connected between the high-voltage terminal and earth.
In DC mode the microammeter is in the return path from the specimen, so it reads the leakage current at the test voltage without calculation. The reading is taken after the voltage has stabilised and again at the end of the hold time. A current that climbs while the voltage is steady is the signal to stop and inspect the specimen.
The manual notes that a capacitor should be added to the test circuit when testing arresters. The capacitor supplies the charge needed during the test and keeps the voltage from collapsing at the reference point. The leakage current at that point is then read on the microammeter and compared with the previous test on the same arrester.
The filter capacitor and the specimen both store charge. After the supply is cut, the specimen is discharged and earthed with a discharge rod, and the capacitor is allowed to discharge through its bleeder. The leads are not touched until both are discharged.
| Mode | Output voltage | Output current | Capacity | Input | Ratio | Temp rise |
|---|---|---|---|---|---|---|
| DC | 70 kV | 100 mA | - | 380 V, 50/26 A | 500 | 10 C / 30 min |
At DC the specimen current is the true leakage current, without the capacitive charging current that flows during an AC test. That makes small changes easier to see.
Yes. In DC mode the panel microammeter reads the current through the specimen, and the value is recorded with the applied voltage and test time.
The manual specifies an added capacitor for arrester tests so that the test circuit can supply the charge needed and hold the reference voltage stable while the leakage current is read.
Send the specimen type, its capacitance and the leakage current range you need to resolve, and we will confirm the XHYB-5/50 DC configuration.