A 60 kV, 2 mA DC high voltage generator set up for zinc oxide arrester testing, where the leakage current at the reference voltage is the value being judged.
Zinc oxide arresters are tested by applying a DC voltage and reading the leakage current at a defined reference point. A 60 kV source covers the arresters used on 10 kV, 35 kV and many 66 kV systems, where the reference voltage sits comfortably inside the 60 kV range.
The 0.75UDC-1mA button sets the reference voltage at 0.75 times the DC 1 mA voltage in a single action. The current at that voltage is then read and compared with the value expected for the arrester. The button removes the arithmetic and the risk of setting the wrong reference on site.
The measured leakage is compared with the manufacturer value and with the previous test on the same arrester. A rise over time matters more than a single reading, which is why the voltage, current and test date should go into the record together.
At 120 W the set is compact and the multiplier is light. It is intended for teams whose DC work is mostly arrester testing, with occasional cable or transformer checks inside the 60 kV range.
| Configuration 60 kV / 2 mA | Output voltage | Output current | Output power | Charging current | Control box | Multiplier |
|---|---|---|---|---|---|---|
| 60 kV / 2 mA | 60 | 2 | 120 | 3 | 11.6 | 2.3 |
| Parameter | Value |
|---|---|
| Voltage measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Current measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Ripple factor | <= 0.5 % |
| 0.75UDC-1mA button | Precision <= 1.0 % |
| Working mode | 30 min at rated load; 10 min at 1.1 times rated voltage |
60 kV covers the reference voltage of arresters used on 10 kV to 66 kV systems. A higher voltage is only needed when the arrester rating itself requires it.
It sets the output to 0.75 times the DC 1 mA voltage, which is the reference point used for zinc oxide arrester leakage measurement.
Yes, within 60 kV and 2 mA. For longer cable or higher capacitance the 5 mA configuration charges the specimen faster.
Send the arrester rating and the reference voltage from the nameplate, and we will confirm that the 60 kV / 2 mA configuration covers it.