A 60 kV, 2 mA DC test set built around the leakage current reading: what the current is at each voltage step, and what it does over time.
A DC withstand test passes or fails on whether the insulation holds. A leakage test adds the current that flows while it holds. That current responds to moisture, contamination, tracking and ageing long before a breakdown occurs, which is why it is recorded at every step rather than only at the end.
The current display resolves small changes, and the output ripple is held within the figure stated for the platform so that ripple does not appear as current noise. Voltage and current are taken from the high voltage side, which keeps the reading tied to the specimen rather than to the control box.
Leakage readings are only as good as the connection. Clean, dry terminations, short high voltage leads and a consistent guard arrangement matter more at the microamp level than at the milliamp level. The same lead arrangement should be used each time so that the trend is comparable.
The set covers arresters, short cable sections, small transformers and motors inside 60 kV. It is chosen when the work is diagnostic and the specimen capacitance is modest, not when a long cable has to be charged quickly.
| Configuration 60 kV / 2 mA | Output voltage | Output current | Output power | Charging current | Control box | Multiplier |
|---|---|---|---|---|---|---|
| 60 kV / 2 mA | 60 | 2 | 120 | 3 | 11.6 | 2.3 |
| Parameter | Value |
|---|---|
| Voltage measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Current measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Ripple factor | <= 0.5 % |
| 0.75UDC-1mA button | Precision <= 1.0 % |
Voltage and current are sampled on the high voltage side and shown together, so the current corresponds to the voltage actually applied to the specimen.
Ripple is kept within the stated limit so that it does not appear as current noise. Stable leads and clean terminations matter as much as the source.
Within 60 kV and 2 mA, yes, for short sections. Longer cable is better served by the 5 mA configuration.
Send the specimen type, its capacitance and the current you expect to resolve, and we will confirm the configuration and the lead set.