A 120 kV, 2 mA DC hipot tester for power cable withstand testing, covering 35 kV and 66 kV cable classes and the leakage reading that goes with the withstand result.
Cable insulation tests are limited by both voltage and charging current. 120 kV covers the 35 kV and 66 kV classes, and 2 mA is enough for the cable lengths usually tested from a single termination. For very long sections, calculate the charging current before the test and compare it with the output rating.
The usual sequence is a voltage step to the specified test level, a hold for the specified time, then a controlled reduction and discharge. The leakage current is recorded at each step. A rise in current without a rise in voltage is the signal to stop and investigate.
Voltage and current are sampled on the high voltage side and shown together, so the leakage value corresponds to the voltage actually applied. The reading, the cable temperature and the ambient conditions should go into the record, because a cable tested cold and one tested after loading are not directly comparable.
The test area is barriered, the far end is guarded, and the cable is earthed and discharged before anyone touches it. The set discharges the specimen when the test stops, but the manual earth-and-discharge step is still required.
| Configuration 120 kV / 2 mA | Output voltage | Output current | Output power | Charging current | Control box | Multiplier |
|---|---|---|---|---|---|---|
| 120 kV / 2 mA | 120 | 2 | 240 | 3 | 13 | 3.2 |
| Parameter | Value |
|---|---|
| Voltage measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Current measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Ripple factor | <= 0.5 % |
| 0.75UDC-1mA button | Precision <= 1.0 % |
| Working mode | 30 min at rated load; 10 min at 1.1 times rated voltage |
35 kV and 66 kV cable classes, with the test voltage set by the standard applied on site. Longer sections should be checked against the 2 mA charging current.
30 minutes at rated load, with a short-term rating of 10 minutes at 1.1 times rated voltage.
Yes. Voltage and current are displayed together, and the leakage at each step is recorded.
Send the cable class, length and capacitance per phase, and we will confirm whether the 120 kV / 2 mA configuration covers the charging current and the test voltage.