A 120 kV, 2 mA DC hipot tester for high voltage arresters, where the 0.75UDC-1mA reference point and a stable leakage reading decide the result.
Arresters on 110 kV and 220 kV systems have reference voltages that sit above the 60 kV range. A 120 kV source covers the arresters that fall inside it, with the exact reference taken from the arrester nameplate rather than from the system voltage.
The DC 1 mA voltage is first established, then the output is set to 0.75 times that value with the single-touch button. The leakage current at that voltage is read and compared with the manufacturer value and with the previous test on the same unit. The button removes the manual calculation and the setting error that comes with it.
An arrester that draws more current at the same reference voltage than it did last time is changing. Moisture ingress, ageing of the zinc oxide blocks and contamination of the housing all show up this way. The absolute value matters less than the direction and rate of change.
Record the reference voltage, the leakage current, the ambient temperature and the humidity together. A reading without the conditions is difficult to defend when the next test is compared with it.
| Configuration 120 kV / 2 mA | Output voltage | Output current | Output power | Charging current | Control box | Multiplier |
|---|---|---|---|---|---|---|
| 120 kV / 2 mA | 120 | 2 | 240 | 3 | 13 | 3.2 |
| Parameter | Value |
|---|---|
| Voltage measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Current measurement error | <= 1.0 % (full scale) +/- 1 digit |
| Ripple factor | <= 0.5 % |
| 0.75UDC-1mA button | Precision <= 1.0 % |
Arresters whose reference voltage falls inside the 120 kV range, including many 110 kV and 220 kV system arresters. The nameplate reference voltage decides, not the system voltage.
The DC 1 mA voltage is found first, then the 0.75UDC-1mA button sets 0.75 times that value. The leakage at that point is the recorded result.
Yes, within 120 kV and 2 mA, though larger cable sections may need the 5 mA configuration.
Send the arrester nameplate reference voltage and the expected leakage range, and we will confirm that the 120 kV / 2 mA configuration covers it.